Parameterization
5.3 Parameter assignment with FB 45/55 and FC 56
ASM 456 interface module
Operating Instructions, 07/2015, J31069-D0162-U001-A6-7618
37
Input parameters for ASM 456 with FC 56
The assignment is made in UDT 10.
Table 5- 3
Input parameters for ASM 456 with FC 56
Address
Name
Permissible values
Comment
+0.0
ASM_address
0, 4, 8, 12, ...
Each ASM 456 occupies four bytes of I/O
in the I/O area of the controller.
+2.0
ASM channel
1
1 channel per ASM
+8.0
MDS IO control
B#16#0, 1, 4, 5
Enable/disable presence check
+9.0
ECC_mode
TRUE, FALSE
TRUE is only permitted
when MOBY mode is set to 1
+9.2
priority_RW
TRUE, FALSE
+9.3
priority_RWD
TRUE, FALSE
+10.0
MOBY mode
B#16#1, 4, 5, 6
MOBY I/U
+11.0
scanning_time
MOBY I:
B#16#00 ... FF
A value not equal to 00 is only of any
use if MOBY_mode has been parameterized
accordingly
MOBY U:
B#16#00 ... C8
+12.0
SLG_number
B#16#0001 ... FFFF
With FFFF, the test function is switched
on
+14.0
distance_limiting
B#16#05, 0A, 0F, 14,
19, 1E, 23
MOBY U
+15.0
multitag
MOBY I:
B#16#1
MOBY I/U
MOBY U:
B#16#01 ... 0C
+16.0
field ON control
B#16#0, 1, 2
MOBY U
+17.0
field ON time
B#16#00 ... FF
MOBY U