Siemens Building Technologies, Inc.
P84395-003 B
Sheet 2 of 3
Table 3: Current Ratings (AMPS)
Maximum RMS Current with Hi dBA Setting
Voltage 15cd
30cd
75cd
95cd
DC 16.0-33.0VDC
0.101 0.147 0.235 0.303
FWR 16.0-33.0VRMS
0.144
0.202
0.324
0.424
Maximum RMS Current with Med dBA Setting
Voltage 15cd
30cd
75cd
95cd
DC 16.0-33.0VDC
0.085 0.130 0.213 0.285
FWR 16.0-33.0VRMS
0.132
0.185
0.312
0.414
Maximum RMS Current with Low dBA Setting
Voltage 15cd
30cd
75cd
95cd
DC 16.0-33.0VDC
0.079 0.120 0.210 0.279
FWR 16.0-33.0VRMS
0.122
0.180
0.308
0.409
Note: These notification appliances are UL Listed as “Special Application”. They are intended to be used only with Siemens notification appliance
circuits.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S
PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS
OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT
IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
CANDELA AND SOUND OUTPUT SETTINGS:
To set the candela, slide the switch to the desired setting. The setting is indicated by the pointer and label visible on the bottom side of the lens.
Figure 1:
Figure 2: Showing Location of Jumper Plug
95
CANDELA
POINTER
BOTTOM VIEW
30
15
75
CODE 3
HI
MED
LO
CANDELA
SLIDE
SWITCH
Back View
Factory setting is on Medium dB, Code 3 (or March Time) and 15 candela.
THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION. WHEN
CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE. AFTER CHANGING THE
CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION
THE AUDIBLE STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE
INSTALLED. THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS.
Figure 3: Jumper plug settings for High, Medium, Low and Code 3
Figure 4: Jumper plug setting for Continuous Horn
SHOWN SET ON HIGH dB
SHOWN SET ON MED dB
SHOWN SET ON LOW dB
HI
MED
LOW
(Use needle nose pliers to pull and properly set the jumper plugs)
CODE 3
TURN PLUG 90°
No jumper plug is needed for continuous horn setting.
However, it is recommended that the jumper plug be
retained in the unit for future use (if needed) as shown in
Figure 4.
NOTE:
The AS-MC-C must be set for Code 3 (or March Time) when used with a synchronized notification appliance circuit (NAC).
WIRING AND MOUNTING INFORMATION:
CAUTION:
The following figures (A-D) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting
option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could
damage the product. Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit,
especially if sheathed multiconductor cable or 3/4" conduit fittings are used.