Siemens Building Technologies, Inc
. P84449-003 B
Sheet 2 of 4
Table 3: Current Ratings (AMPS)
Maximum RMS Current with Hi dBA Setting
Voltage 135cd
185cd
DC 16.0-33.0VDC
0.356
0.488
FWR 16.0-33.0VRMS
0.499
0.705
Maximum RMS Current with Med dBA Setting
Voltage
135cd
185cd
DC 16.0-33.0VDC
0.361
0.493
FWR 16.0-33.0VRMS
0.509
0.716
Maximum RMS Current with Low dBA Setting
Voltage 135cd
185cd
DC 16.0-33.0VDC
0.356
0.499
FWR 16.0-33.0VRMS
0.488
0.705
Note:
These notification appliances are UL Listed as “Special Application.” They are intended to be used only with Siemens notification appliance circuits.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S
PRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF
ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE
RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
CANDELA AND SOUND OUTPUT SETTINGS:
To set the candela, slide the switch to the desired setting. The setting is indicated by the pointer and label visible on the bottom side of the lens.
Figure 1:
Figure 2: Showing Location of Jumper Plug
135
185
CANDELA
POINTER
BOTTOM VIEW
CODE 3
HI
MED
LO
CANDELA
SLIDE
SWITCH
BACK VIEW
Factory setting is on Medium dB, Code 3 (or March Time) and 185 candela.
WARNING: THE AUDIBLE STROBE APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE
THEY ARE INSTALLED. THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS.
Figure 3: Jumper plug settings for High, Medium, Low and Code 3
(or March Time)
Figure 4: Jumper plug setting for Continuous Horn
SHOWN SET ON HIGH dB
SHOWN SET ON MED dB
SHOWN SET ON LOW dB
HI
MED
LOW
(Use needle nose pliers to pull and properly set the jumper plugs)
CODE 3
TURN PLUG 90°
No jumper plug is needed for continuous horn setting.
However, it is recommended that the jumper plug be retained in
the unit for future use (if needed) as shown in Figure 4.
NOTE:
The AS-HMC must be set for Code 3 (or March Time) when used with a synchronized notification appliance circuit (NAC).