appliances are specified, the strobe intensity shall have  

field selectable settings and shall be rated per UL Stan-

dard 1971 at 15/30/75/110 or 135/185 candela for wall 

mount and 15/30/75/95 or 115/177 candela for ceiling 

mount.  The selector switch for selecting the candela 

shall be tamper resistant.  
When synchronization is required, the appliance shall 

be synchronized using the Siemens DSC sync modules, 

FS-250 panel, XLS panel, or PAD-3 power supply with 

built-in sync protocol.  The strobes shall not drift out of 

synchronization at any time during operation.  If the sync 

module or Power Supply fails to operate, (i.e., contacts 

remain closed), the strobe shall revert to a non-synchro-

nized flash-rate.  The appliance shall also be designed 

so that the audible signal may be silenced while main-

taining strobe activation when used with Siemens syn-

chronization.
The Series AS Audible Strobe and Series AH Audible 

shall incorporate a Patented Universal Mounting Plate 

that shall allow mounting to a single-gang, double-gang, 

4-inch square, 100mm European type backboxes, or the 

SHBBS Surface Backbox.  
All notification appliances shall be listed for Special Ap-

plications.
•   Strobes are designed to flash at 1 flash per second 

minimum over their “Regulated Input Voltage Range”.  

Note that NFPA-72 specifies a flash rate of 1 to 2 

flashes per second and ADA Guidelines specify a flash 

rate of 1 to 3 flashes per second.

•   All candela ratings represent minimum effective Strobe 

intensity based on UL Standard 1971. 

Technical Information

For complete technical information, please consult the 

relevant installation sheets as well as the Siemens  

Compatibility Guide.

Model  

Number

Order Code

Wall 

Mount

Ceiling 

Mount

Mounting Options**

Agency Approvals

UL ULC CSFM FM

AS-MC-R

500-636010

X

-

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AS-MC-W

500-636011

X

-

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AS-HMC-R

500-636012

X

-

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AS-HMC-W

500-636013

X

-

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AS-MC-CR

500-636006

-

X

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AS-MC-CW

500-636007

-

X

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AS-HMC-CR

500-636008

-

X

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AS-HMC-CW

500-636009

-

X

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AS-75-R-WP

500-636016

X

-

I

X

#

#

#

AS-75-CR-WP

500-636015

-

X

I

X

#

#

#

AH-R

500-636003

X

X

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AH-W

500-636004

X

X

A,B,D,E,F,G,J,N,R,X

X

#

#

#

AH-R-WP

500-636005

X

X

K

X

#

#

#

Ordering Information / Mounting Requirements / Approvals

X = listed/approved 

# = pending 

* = Refer to Data Sheet #2585 for mounting options.

Siemens Building Technologies

Fire Safety

Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (973) 593-6670
Website: www.sbt.siemens.com/fis

7/07

5M

SFS-IG

Printed in U.S.A.

Fire Safety
2 Kenview Boulevard
Brampton, Ontario
Canada L6T 5E4
Tel: (905) 799-9937
FAX: (905) 799-9858

July 2007

New Issue

WARNING:

  PLEASE  READ  THESE  SPECIFICATIONS AND  INSTALLATION  INSTRUCTIONS  CAREFULLY  BEFORE  

USING, SPECIFYING OR APPLYING THIS PRODUCT.  FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, 

CAUTIONS AND  WARNINGS  COULD  RESULT  IN  IMPROPER APPLICATION,  INSTALLATION AND/OR  OPERATION  

OF THESE  PRODUCTS  IN AN  EMERGENCY  SITUATION,  WHICH  COULD  RESULT  IN  PROPERTY  DAMAGE, AND  

SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

Summary of Contents for AH Series

Page 1: ... FS 250 panel XLS panel or PAD 3 power supply with built in sync protocol synchronization of the continuous horn tone provides the temporal code 3 tone man dated by NFPA 72 simultaneously for all audible appli ances This ensures a distinct temporal code 3 pattern when 2 or more audibles are within hearing distance If not synchronized the temporal sound could overlap and not be distinctive At the s...

Page 2: ...e Strobe intensity based on UL Standard 1971 Technical Information For complete technical information please consult the relevant installation sheets as well as the Siemens Compatibility Guide Model Number Order Code Wall Mount Ceiling Mount Mounting Options Agency Approvals UL ULC CSFM FM AS MC R 500 636010 X A B D E F G J N R X X AS MC W 500 636011 X A B D E F G J N R X X AS HMC R 500 636012 X A...

Page 3: ...of circuit wiring by an FACP NOTE All Canadian installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems CAN ULC S524 01 and Canadian Electrical Code Part 1 Final acceptance is subject to authority having jurisdiction AHJ NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit SPECIFICATIONS Tabl...

Page 4: ...SOUND OUTPUT SETTINGS To set the candela slide the switch to the desired setting The setting is indicated by the pointer and label visible on the bottom side of the lens Figure 1 Figure 2 Showing Location of Jumper Plug Back View 15 75 1 30 1 0 CANDELA POINTER BOTTOM VIEW CODE 3 HI MED LO CANDELA SLIDE SWITCH Factory setting is on Medium dB Code 3 or March Time and 15 candela WARNING THE CANDELA S...

Page 5: ...wiring diagrams is for the operation of the appliances The polarity is reversed by the FACP during supervision MOUNTING PROCEDURES 1 This model can be flush mounted to a standard single gang backbox Figure A 4 backbox Figure B or double gang backbox Figure C They can also be surface mounted to a 4 or 100mm backbox Figure B a double gang backbox Figure C or a SHBBS surface backbox Figure D Mounting...

Page 6: ...S INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE 5 Hz AT THE OPERATING VOLTAGE OF THE STROBES IT IS STRONGLY RECOMMENDED THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS STANDARDS REGULATIONS CODES AND GUIDELINES NOTE This equipment has been tested and found to comply with the limits for ...

Page 7: ...or compatibility with standard reverse polarity supervision of circuit wiring by a FACP NFPA 72 ANSI 117 1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer higher intensity strobes within the same protected area NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit SPECIFICATIONS Table 1 UL Ratings Model Operating Voltage Spe...

Page 8: ...O CANDELA SLIDE SWITCH Back View Factory setting is on Medium dB Code 3 or March Time and 15 candela THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH MAKE CERTAIN THAT IT CLICKS IN PLACE AFTER CHANGING THE CANDELA SETTING THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION THE AUDIBLE STRO...

Page 9: ...ld wires in the backbox so that they use minimum space and produce minimum stress on the product This is especially important for stiff heavy gauge wires and wires with thick insulation or sheathing 5 Thread the 4 field wires through the opening of the UMP Mount the UMP to backbox 6 Connect 4 field wires to the AS MC C terminal block polarity must be observed Bend the 4 field wires up 90 o at the ...

Page 10: ...ion signaling The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose NFPA 72 ANSI 117 1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer higher intensity strobes within the same protected area NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit SPECIFICATIONS Table 1 UL Ratings Model...

Page 11: ...tting is indicated by the pointer and label visible on the bottom side of the lens Figure1 Figure 2 Showing Location of Jumper Plug 115 177 CANDELA POINTER BOTTOM VIEW CODE 3 HI MED LO CANDELA SLIDE SWITCH Back View Factory setting is on Medium dB Code 3 or March Time and 177 candela WARNING THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION WHEN CHAN...

Page 12: ...uld result in insufficient wiring space for the signaling appliance 4 When terminating field wires do not use more lead length than required Excess lead length could result in insufficient wiring space for the signaling appliance Position the field wires in the backbox so that they use minimum space and produce minimum stress on the product This is especially important for stiff heavy gauge wires ...

Page 13: ...itation Guidelines in using fewer higher intensity strobes within the same protected area NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit CAUTION NOT RECOMMENDED FOR USE AT REFRIGERATOR FREEZER DOOR ENTRANCES OR OTHER AREAS WITH PERSISTENT CONDENSATION SPECIFICATIONS Table 1 Models and Ratings UL Rated Strobe Candela cd Maximum RMS Curre...

Page 14: ...NSTALLATION WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH MAKE CERTAIN THAT IT CLICKS IN PLACE AFTER CHANGING THE CANDELA SETTING THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION Figure 3 Jumper plug settings for High Medium Low and Code 3 or March Time Figure 4 Jumper plug setting for Continuous Horn SHOWN SET ON HIGH dB SHOWN SET ON MED dB SHOWN SET ON LOW dB HI MED LOW Use nee...

Page 15: ... SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY STROBE REFLECTIONS IN A GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE TO MINIMIZE THIS POSSIBLE HAZARD SIEMENS STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW WHICH EXCEEDS FIVE 5 Hz AT THE OPERATING VOLTAGE OF THE STROBES SIEMENS ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND ...

Page 16: ...y for fire evacuation signaling and not for any other purpose SPECIFICATIONS Table 1 UL ULC Listed Models and Ratings Maximum RMS Current AMPS DC FWR Model Operating Voltage Special Application Per UL 464 VDC VRMS ULC Voltage Range VDC VRMS Lo Med Hi Lo Med Hi AH 16 33 20 31 0 021 0 043 0 080 0 041 0 051 0 090 Available in red or white Table 1A ULC Current Ratings Average Current AMPS Model ULC Vo...

Page 17: ...PPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG IN ACCORDANCE WITH THESE INSTRUCTIONS SOUND OUTPUT SPL SETTINGS Figure 1 Showing Location of Jumper Plug CODE 3 HI MED LO Factory setting is on medium dB and code 3 or March Time Figure 2 Jumper plug settings for high medium low and code 3 or March T...

Page 18: ...x Figure C They can also be surface mounted to a 4 square or 100mm backbox Figure B a double gang backbox Figure C or a SHBBS surface backbox Figure D 2 All models are equipped with a Universal Mounting Plate UMP 3 Mounting hardware for each mounting option is supplied For proper mounting be sure to use the mounting screws supplied with the unit 4 Conduit entrances to the backbox should be selecte...

Page 19: ...her purpose SPECIFICATIONS Table 1 UL ULC Listed Models and Ratings Maximum RMS Current AMPS DC FWR Model Operating Voltage Special Application Per UL464 VDC VRMS ULC Voltage Range VDC VRMS Lo Med Hi Lo Med Hi AH R WP 16 33 20 31 0 023 0 049 0 090 0 046 0 057 0 096 Table 1A ULC Current Ratings 24VDC Models Average Current AMPS Model ULC Voltage VDC VRMS Lo Med Hi 20 0 016 022 039 24 0 019 029 056 ...

Page 20: ... DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE INSTALLED THIS IS DONE BY PROPERLY INSERTING A JUMPER PLUG IN ACCORDANCE WITH THESE INSTRUCTIONS SOUND OUTPUT SPL SETTINGS Figure 1 Showing Location of Jumper Plug J1 and J1 AUD P83511 J2 J1 H M L C O D E 3 J2 J1 H M L D 3 E O C Factory setting is on Medium dB and Code 3 or March Time Figure 2 Jumper Plug Settings for High Medium Low dB Code...

Page 21: ...ring space for the signaling appliance 7 Do not pass additional wires used for other than the signaling appliance through the backbox Such additional wires could result in insufficient wiring space for the signaling appliance 8 The knock out opening on the backbox is sized for a conduit and matching connector Be sure that a proper watertight conduit fitting is used to connect the backbox for outdo...

Page 22: ...ling The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose NFPA 72 ANSI 117 1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer higher intensity strobes within the same protected area NOTE Refer to P N 315 096363 for the maximum number of appliances on a single notification appliance circuit SPECIFICATIONS Table 1 UL Ratings Model Operatin...

Page 23: ...ROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS CANDELA AND SOUND OUTPUT SETTINGS To set the candela slide the switch to the desired setting The setting is indicated by the pointer and label visible on the bottom side of the lens Figure 1 Figure 2 Showing Location of Jumper Plug 135 185 CANDELA POINTER BOTTOM VIEW CODE 3 HI MED LO CANDELA SLIDE SWITCH BACK VIEW Factory setting is o...

Page 24: ...he FACP during supervision MOUNTING PROCEDURES 1 This model can be flush mounted to a standard single gang backbox Figure A 4 backbox Figure B or double gang backbox Figure C They can also be surface mounted to a 4 or 100mm backbox Figure B a double gang backbox Figure C or a SHBBS surface backbox Figure D Mounting hardware for each mounting option is supplied For proper mounting be sure to use th...

Page 25: ...N THE FIELD OF VIEW WHICH EXCEEDS FIVE 5 Hz AT THE OPERATING VOLTAGE OF THE STROBES SIEMENS ALSO STRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS STANDARDS REGULATIONS CODES AND GUIDELINES NOTE This equipment has been tested and found to comply with the limits for a Class B digital appliance pursuant to Part 15 o...

Reviews: