appliances are specified, the strobe intensity shall have
field selectable settings and shall be rated per UL Stan-
dard 1971 at 15/30/75/110 or 135/185 candela for wall
mount and 15/30/75/95 or 115/177 candela for ceiling
mount. The selector switch for selecting the candela
shall be tamper resistant.
When synchronization is required, the appliance shall
be synchronized using the Siemens DSC sync modules,
FS-250 panel, XLS panel, or PAD-3 power supply with
built-in sync protocol. The strobes shall not drift out of
synchronization at any time during operation. If the sync
module or Power Supply fails to operate, (i.e., contacts
remain closed), the strobe shall revert to a non-synchro-
nized flash-rate. The appliance shall also be designed
so that the audible signal may be silenced while main-
taining strobe activation when used with Siemens syn-
chronization.
The Series AS Audible Strobe and Series AH Audible
shall incorporate a Patented Universal Mounting Plate
that shall allow mounting to a single-gang, double-gang,
4-inch square, 100mm European type backboxes, or the
SHBBS Surface Backbox.
All notification appliances shall be listed for Special Ap-
plications.
• Strobes are designed to flash at 1 flash per second
minimum over their “Regulated Input Voltage Range”.
Note that NFPA-72 specifies a flash rate of 1 to 2
flashes per second and ADA Guidelines specify a flash
rate of 1 to 3 flashes per second.
• All candela ratings represent minimum effective Strobe
intensity based on UL Standard 1971.
Technical Information
For complete technical information, please consult the
relevant installation sheets as well as the Siemens
Compatibility Guide.
Model
Number
Order Code
Wall
Mount
Ceiling
Mount
Mounting Options**
Agency Approvals
UL ULC CSFM FM
AS-MC-R
500-636010
X
-
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AS-MC-W
500-636011
X
-
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AS-HMC-R
500-636012
X
-
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AS-HMC-W
500-636013
X
-
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AS-MC-CR
500-636006
-
X
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AS-MC-CW
500-636007
-
X
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AS-HMC-CR
500-636008
-
X
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AS-HMC-CW
500-636009
-
X
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AS-75-R-WP
500-636016
X
-
I
X
#
#
#
AS-75-CR-WP
500-636015
-
X
I
X
#
#
#
AH-R
500-636003
X
X
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AH-W
500-636004
X
X
A,B,D,E,F,G,J,N,R,X
X
#
#
#
AH-R-WP
500-636005
X
X
K
X
#
#
#
Ordering Information / Mounting Requirements / Approvals
X = listed/approved
# = pending
* = Refer to Data Sheet #2585 for mounting options.
Siemens Building Technologies
Fire Safety
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (973) 593-6670
Website: www.sbt.siemens.com/fis
7/07
5M
SFS-IG
Printed in U.S.A.
Fire Safety
2 Kenview Boulevard
Brampton, Ontario
Canada L6T 5E4
Tel: (905) 799-9937
FAX: (905) 799-9858
July 2007
New Issue
WARNING:
PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE
USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS,
CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION
OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.