2000590-001
Data Communications Setup
••
35
Setting Network Address & Loop and Unit Numbers,
Continued
3. Press
↵
↵
Enter
.
The following message appears Configuration Change verified.
Type: reset - to save configuration changes
4. To save your entry, at the Local
>>
prompt type:
reset
5. To configure the ANG_EN subnetmask, at the Local
>>
prompt type:
config netmask xxx.xxx.xxx.xxx
Where xxx.xxx.xxx.xxx is the subnet mask for your network. Typi-
cally, this would be 255.255.0.0 or 255.255.255.0.
6. Press
↵
↵
Enter
, and save your entry by typing at the Local
>>
prompt:
reset.
7. To configure the ANG_EN Loop number, at the Local
>>
prompt type:
config loop x
Where x is a number in the range from 1 - 8 depending on the ADH
Loop number of the Units to be connected directly to the ANG_EN
ADH bus.
8. Press
↵
↵
Enter
, and save your entry by typing at the Local
>>
prompt:
reset
9. To configure the ANG_EN Unit number at the Local
>>
prompt type:
config unit x
Where x is a number in the range of 0 - 31. Typically this number is
set to zero to give the ANG_EN the top priority on its local ADH bus.
If the ANG_EN is connected to an NIU the Unit number must be in
the range of 1 - 31. Note parameters are not saved until the
ANG_EN is reset.