MSCDN – MP2A Relay Settings
2) 27 status inputs represents maximum configuration.
1.6 Reylogic Control Menu
Description Range
Default
Setting
General Logic
Selects whether the logic diagram is enabled, if disabled then
no outputs will be driven.
Enable, Disable
Enable
1.7 Reylogic Element Menu
Description Range
Default
Setting
Trip Cct Pickup Delay
0,1…60000 ms
400 ms
1.8 Output Relay Menu
Description Range
Default
Setting
R1 49 Alarm
Resistor 1 Thermal capacity alarm operated
NONE, 1…29
1
2
R1 49 Trip
Resistor 1 Thermal capacity trip operated
NONE, 1…29
1
4,5
R2 49 Alarm
Resistor 2 Thermal capacity alarm operated
NONE, 1…29
1
2
R2 49 Trip
Resistor 2 Thermal capacity trip operated
NONE, 1…29
1
4,5
R1 50
Resistor 1 Open Circuit DTL Overcurrent operated
NONE, 1…29
1
3
R2 50
Resistor 2 Open Circuit DTL Overcurrent operated
NONE, 1…29
1
3
Phase A
A phase A element operated
NONE, 1…29
1
NONE
Phase B
A phase B element operated
NONE, 1…29
1
NONE
Phase C
A phase C element operated
NONE, 1…29
1
NONE
General Starter
A starter element is picked up
NONE, 1…29
1
NONE
General Trip
An element has operated. Useful when testing individual
functions!
NONE, 1…29
1
NONE
Trip Circuit Fail
A trip circuit has failed, look at status input Leds to find out
which one
NONE, 1…29
1
NONE
New Data Stored
The waveform recorder has stored new information Note: this
is a pulsed output
NONE, 1…29
1
NONE
Aux I/P 1 Operated
DC Status 1 has operated
NONE, 1…29
1
NONE
Aux I/P 2 Operated
NONE, 1…29
1
NONE
Aux I/P 3 Operated
NONE, 1…29
1
NONE
Aux I/P 4 Operated
2
NONE,
1…29
1
NONE
Aux I/P 5 Operated
2
NONE,
1…29
1
NONE
Aux I/P 6 Operated
2
NONE,
1…29
1
NONE
Aux I/P 7 Operated
2
NONE,
1…29
1
NONE
Aux I/P 8 Operated
2
NONE,
1…29
1
NONE
Aux I/P 9 Operated
2
NONE,
1…29
1
NONE
Aux I/P 10 Operated
2
NONE,
1…29
1
NONE
Aux I/P 11 Operated
2
NONE,
1…29
1
NONE
Aux I/P 12 Operated
2
NONE,
1…29
1
NONE
Aux I/P 13 Operated
2
NONE,
1…29
1
NONE
Aux I/P 14 Operated
2
NONE,
1…29
1
NONE
Aux I/P 15 Operated
2
NONE,
1…29
1
NONE
Aux I/P 16 Operated
2
NONE,
1…29
1
NONE
Aux I/P 17 Operated
2
NONE,
1…29
1
NONE
Aux I/P 18 Operated
2
NONE,
1…29
1
NONE
Aux I/P 19 Operated
2
NONE,
1…29
1
NONE
©2010 Siemens Protection Devices Limited
Chapter 3 Page 5 of 14