MSCDN – MP2A Relay Settings
1 MSCDN-MP2A Relay Setting List
1.1 System Config Menu
Description Range
Default
Setting
Active Group
Selects which settings group is currently activated
1,2…4
1
View/Edit Group
Selects which settings group is currently being displayed
1,2…4 1
Default Screens Timer
Selects the time delay after which, if no key presses have
been detected, the relay will begin to poll through any
screens which have been selected as default instruments
screens
OFF, 1,2,5,10,15,30,60
min
60 min
Backlight timer
Controls when the LCD backlight turns off
OFF, 1,2,5,10,15,30,60
min
5 Min
Date Date
1/1/1980
Time Time
00:00:00
Clock Sync. From Status
Real time clock may be synchronised using a status input
(See Clock Sync. in Status Input Menu)
Disabled,
Seconds,Minutes
Minutes
Operating Mode
To allow access to change configuration files using Reylogic
Toolbox the relay must be placed Out Of Service.
Local, Remote, Local Or
Remote, Out Of Service
Local Or Remote
Change Password
Allows a 4 character alpha code to be entered as the
password. Note that the display shows a password
dependant encrypted code on the second line of the display
AAAA…ZZZZ
“NONE” displayed as
“NOT ACTIVE”
Relay Identifier
An alphanumeric string shown on the LCD normally used to
identify the circuit the relay is attached to or the relays
purpose
Up to 16 characters
MSCDN-MP2A
1.2 CT/VT Config Menu
Description Range
Default
Setting
R1 Input
Selects whether 1 or 5 Amp terminals are being used for
resistor 1
1,5 A
1 A
R1 CT Ratio
Resistor R1 CT ratio to scale primary current instruments
1:0.2…5000:7 2000:1
R2 Input
Selects whether 1 or 5 Amp terminals are being used for
resistor 2
1,5 A
1 A
R2 CT Ratio
Resistor R2 CT ratio to scale primary current instruments
1:0.2…5000:7 2000:1
1.3 Thermal Menu
Description Range
Default
Setting
G
n
R1 49 Thermal Overload
Selects whether the thermal overload protection element is
enabled for Resistor R1
Disabled, Enabled
Disabled
G
n
R1 49 Overload Setting
Pickup level
0.1,0.11…3 xIn
1.05 xIn
G
n
R1 49 Time Constant
Thermal time constant
1, 2…10000 s
10 s
G
n
R1 49 Capacity Alarm
Selects whether thermal capacity alarm enabled
Disabled, 50,51…100 %
Disabled
R1 49 Reset Therm State
Control that allows thermal state to be manually reset
NO, YES
NO
G
n
R2 49 Thermal Overload
Selects whether the thermal overload protection element is
enabled for Resistor R2
Disabled, Enabled
Disabled
G
n
R2 49 Overload Setting
Pickup level
0.1,0.11…3 xIn
1.05 xIn
G
n
R2 49 Time Constant
Thermal time constant
1, 2…10000 s
10 s
G
n
R2 49 Capacity Alarm
Selects whether thermal capacity alarm enabled
Disabled, 50,51…100 %
Disabled
R2 49 Reset Therm State
Control that allows thermal state to be manually reset
NO, YES
NO
©2010 Siemens Protection Devices Limited
Chapter 3 Page 3 of 14