!PPENDIX
3$
6
# ' #
Annunciations 7SD502 for PC, LC-display and binary inputs/outputs
µµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµµ
FNo. - Function number of annunciation
Op/Ft - Operation/Fault annunciation
C/CG: Coming/Coming and Going annunciation
M
: Measurand
E
- Earth fault annunciation
IOT
- I: can be marshalled to binary input
O: can be marshalled to binary output (LED, signal relay)
T: can be marshalled to trip relay
¬¬¬¬ª¬¬¬¬¬¬¬¬¬¬¬¬¬ª¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬ª¬¬ª¬¬ª¬ª¬¬¬§
FNo.Abbreviation Meaning
OpFtEIOT
«¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
3>Time Synchro>Time synchronization
C IO
4>Start FltRec>Start fault recording
C IO
5>LED reset
>Reset LED indicators
IO
7>ParamSelec.1>Parameter set selection 1 (with No.8) IO
8>ParamSelec.2>Parameter set selection 2 (with No.7) IO
11>Annunc. 1
>User defined annunciation 1
CG IOT
12>Annunc. 2
>User defined annunciation 2
CG IOT
13>Annunc. 3
>User defined annunciation 3
CG IOT
14>Annunc. 4
>User defined annunciation 4
CG IOT
51Dev.operativeDevice operative / healthy
CG O
56Initial startInitial start of processor system
C
60LED reset
LED Reset
C
95Param.runningParameters are being set
CG O
96Param. Set A Parameter set A is active
CG O
97Param. Set B Parameter set B is active
CG O
98Param. Set C Parameter set C is active
CG O
99Param. Set D Parameter set D is active
CG O
100Wrong SW-versWrong software-version
C
101Wrong dev. IDWrong device identification
C
110Annunc. lost Annunciations lost (buffer overflow)
C
111Annu. PC lostAnnunciations for PC lost
C
115Flt.Buff.OverFault annunciation buffer overflow
C
120Oper.Ann.InvaOperational annunciations invalid
CG
121Flt.Ann.InvalFault annunciations invalid
CG
123Stat.Buff.InvStatistic annunciation buffer invalid CG
124LED Buff.InvaLED annunciation buffer invalid
CG
129VDEW-StateInvVDEW state invalid
CG
135Chs Error
Error in check sum
CG
136Chs.A Error Error in check sum for parameter set A CG
137Chs.B Error Error in check sum for parameter set B CG
138Chs.C Error Error in check sum for parameter set C CG
139Chs.D Error Error in check sum for parameter set D CG
142Failure 18V Failure of internal 18 VDC power supplyCG
143Failure 15V Failure of internal 15 VDC power supplyCG OT
144Failure 5V
Failure of internal 5 VDC power supply CG OT
145Failure 0V
Failure of internal 0 VDC power supply CG OT
150Failure I/O Failure in I/O module
CG OT
151Failure I/O 1Failure in I/O module 1
CG OT
154Failure RKA Failure in the RKA module
CG
159LSA disruptedLSA (system interface) disrupted
CG
161I supervisionMeasured value supervision of currents O
162Failure ÌI
Failure: Current summation supervision CG OT
203Flt.RecDatDelFault recording data deleted
C
204Flt.Rec.viaBIFault recording initiated via bin.inputC
¨¬¬¬¬©¬¬¬¬¬¬¬¬¬¬¬¬¬©¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬©¬¬©¬¬©¬©¬¬¬Á