!PPENDIX
3$
6
# ' #
2604 T-I>>
Delay time for I>> TI>>
min. 0.00
s
max. 32.00/Ô
¬¬¬¬
2611 CHARACT
Overcurrent time stage characteristic
DEFINITE TIME
[ ] Definite time
NORMAL INVERSE
[ ] Normal inverse
VERY INVERSE
[ ] Very inverse
EXTREMELY INVERS [ ] Extremely inverse
2612 I>
Pick-up value of overcurrent time stage I>
min. 0.10
I/InLn
max. 30.00
¬¬¬¬
2613 T-I>
Delay time for I> TI>
min. 0.00
s
max. 32.00/Ô
¬¬¬¬
2614 Ip
Pick-up value of overcurrent time stage Ip
min. 0.10
I/InLn
max. 20.00
¬¬¬¬
2615 T-Ip
Time multiplier for Ip (inverse time IDMT) Tp
min. 0.50
s
max. 32.00
¬¬¬¬
2616 RMS FORMAT
Method of RMS calculation for IDMT
WITHOUT HARMON. [ ] Without harmonics
WITH HARMONICS
[ ] With harmonics
2621 MAN.CLOSE
Effective stage after manual closing of CB
INEFFECTIVE
[ ] Ineffective
I>> UNDELAYED
[ ] I>> undelayed
I>/Ip UNDELAYED [ ] I>/Ip undelayed
¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬¬
2700 THERMAL OVERLOAD PROT.
2701 THERMAL OL
State of thermal overload protection
OFF
[ ] off
ON
[ ] on
ALARM ONLY
[ ] Alarm only
BLOCK TRIP REL
[ ] Block trip relay
2702 K-FACTOR
K-factor for thermal overload protection
min. 0.10
max. 4.00
¬¬¬¬
2703 T-CONSTANT
Time constant for thermal overload protection
min. 1.0
min
max. 999.9
¬¬¬¬
2704 Ñ WARN
Thermal warning stage
min. 50
%
max. 100
¬¬¬¬
2705 I WARN
Current warning stage
min. 0.10
I/InLn
max. 4.00
¬¬¬¬