-AINTENANCE AND FAULT TRACING
3$
6
# ' #
2EPLACING THE MINIFUSE
3ELECT A REPLACEMENT FUSE
}
MM %NSURE
THAT THE RATED VALUE TIME LAG MEDIUM SLOW AND
CODE LETTERS ARE CORRECT &IGURE
0REPARE AREA OF WORK PROVIDE CONDUCTIVE SURFACE
FOR THE BASIC MODULE
/PEN HOUSING COVER
(AZARDOUS VOLTAGES CAN BE PRESENT IN
THE DEVICE EVEN AFTER DISCONNECTION OF
THE SUPPLY VOLTAGE OR AFTER REMOVAL OF THE
MODULES FROM THE HOUSING STORAGE CA
PACITORS
7ARNING
,OOSEN THE MODULE USING THE PULLING AIDS PRO
VIDED AT THE TOP AND BOTTOM &IGURE
%LECTROSTATIC DISCHARGES VIA THE COMPO
NENT CONNECTIONS THE 0#" TRACKS OR THE
CONNECTING PINS OF THE MODULES MUST BE
AVOIDED UNDER ALL CIRCUMSTANCES BY PRE
VIOUSLY TOUCHING AN EARTHED METAL SUR
FACE
#AUTION
0ULL OUT THE MODULE AND PLACE ONTO THE CONDUCTIVE
SURFACE
2EMOVE BLOWN FUSE FROM THE HOLDER &IGURE
&IT NEW FUSE INTO THE HOLDER &IGURE
)NSERT DRAWOUT MODULE INTO THE HOUSING ENSURE
THAT THE RELEASING LEVER IS PUSHED FULLY TO THE RIGHT
BEFORE THE MODULE IS PRESSED IN &IGURE
&IRMLY PUSH IN THE MODULE USING THE RELEASING LE
VER &IGURE
#LOSE HOUSING COVER
3WITCH ON THE DEVICE AGAIN )F A POWER SUPPLY FAILURE
IS STILL SIGNALLED A FAULT OR SHORTCIRCUIT IS PRESENT IN
THE INTERNAL POWER SUPPLY 4HE DEVICE SHOULD BE RE
TURNED TO THE FACTORY SEE #HAPTER
!%
!%
!'
2EAR VIEW ON THE REMOVED
BASIC MODULE
-INIFUSE OF THE POWER SUPPLY
MEDIUM SLOW -
RATED
VALUE
AT 5
(.
6
&IGURE
-INIFUSE OF THE POWER SUPPLY
Summary of Contents for 7SD502
Page 148: ... PPENDIX 3 6 PPENDIX ENERAL DIAGRAMS ONNECTION DIAGRAMS 4ABLES ...
Page 176: ... 3 6 ...