Parameter settings
5.2 Configuration via STEP 7 (Basic/Professional)
SIMATIC RF170C
Operating Instructions, 02/2022, J31069-D0176-U001-A6-7618
31
Table 5- 1
Parameters in the "Module parameters" parameter group
Parameter
Parameter value
Default value
Description
User Mode
Ident profile/RFID
standard profile
FB 45 / FC 45
FB 55 / FC 55
Ident profile/RFID
standard profile
Selection depends on the communications
module and Ident system being used. With this
parameter you select the block:
•
Ident profile/RFID standard profile:
The program block for the Ident profile/RFID
standard profile is used on the controller.
•
FB 45 / FC 45:
Single tag mode FB 45 (PROFIBUS/PROFINET)
or FC 45 (PROFIBUS) is used on the
controller.
•
FB 55 / FC 55:
Multitag mode. FB 55 (PROFIBUS/PROFINET)
or FC 55 (PROFIBUS) is used on the
controller.
MOBY Mode
RF200/RF300/RF600;
MV4x0; MOBY U/D
MOBY I/E
MV3xx
Freeport protocol
RF300 filehandler
RF200/RF300/RF600
; MV4x0; MOBY U/D
Selection depends on the communications
module and Ident system being used. With this
parameter, you set the mode of the
communications module.
•
RF200/RF300/RF600; MV4x0; MOBY U/D
•
MOBY I/E
•
MV3xx
•
Freeport protocol
•
RF300 filehandler
1)
Normal addressing: The transponder is
addressed with physical addresses.
Transmission
speed
19.2 kBd
57.6 kBd
115.2 kBd
115.2 kBd
Selection depends on the communications
module and Ident system being used. With this
parameter you set the transmission speed
between the communications module and
reader.
When the RFID reader is connected: After
changing the transmission speed, the reader
must be turned off and on again (cycle power).
When an optical reader is connected: The
transmission speed selected here must match
the transmission speed selected in the firmware
of the reader.
Diagnostics
messages
None
Hard errors
None
Selection depends on the communications
module and Ident system being used. With this
parameter you set whether hardware
diagnostics messages will be reported.
•
None:
Apart from standard diagnostics, no other
alarms are generated.
•
Hard errors:
Critical hardware errors are reported by the
S7 diagnostics.