Technical specifications
8.4 Specifications
Basic Panels
Operating Instructions, 04/2012, A5E02421799-03
137
8.4.5
Ambient conditions
8.4.5.1
Transport and storage conditions
Mechanical and climatic conditions for transportation and storage
The transport and storage conditions of this HMI device exceed requirements in accordance
with IEC 61131-2. The following specifications apply to the transport and storage of an HMI
device in its original packaging.
The climatic conditions conform to the following standards:
●
IEC 60721-3-3, Class 3K7 for storage
●
IEC 60721-3-2, Class 2K4 for transport
Mechanical requirements conform to EC 60721-3-2, Class 2M2.
Type of condition
Permitted range
Drop test (in transport package)
≤ 1 m
Temperature
From –20 to +60 °C
Atmospheric pressure
From 1080 hPa to 660 hPa,
corresponds to an elevation of -1000 to 3500 m
Relative humidity
From 10 % to 90 %, without condensation
Sinusoidal vibration in accordance with
IEC 60068-2-6
5 to 8.4 Hz: 3.5 mm
8.4 to 500 Hz: 9.8 m/s
2
Shock conforming to IEC 60068-2-29
250 m/s
2
, 6 ms, 1000 shocks
NOTICE
Ensure that no condensation (dewing) develops on or inside the HMI device after
transporting it at low temperatures or after it has been exposed to extreme temperature
fluctuations.
The HMI device must have acquired room temperature before it is put into operation. Do
not expose the HMI device to direct radiation from a heater in order to warm it up. If dewing
has developed, wait approximately 4 hours until the HMI device has dried completely
before switching it on.
Proper transport and storage, installation and assembly as well as careful operation and
maintenance are required to ensure trouble-free and safe operation of the HMI device.
The warranty for the HMI device will be deemed void if these stipulations are not heeded.