background image

Industrial I/O-Node - ION PROFIBUS DP SPY T001 

SIPLUS CMS4000

 

Manual - English 
A5E02186042 

 5 / 23

 

2 Scope 

of 

Delivery 

 

2.1 

Scope of Delivery 

What is shipped? 

 Device 

ION PROFIBUS DP SPY T001 

  3-pin plug-in terminal block 

PHOENIX CONTACT, COMBICON, 3 Pin MVSTBW 2,5/3-STF-5,08 

2.2 

Unpacking and Checking 

After unpacking, please check 

  the packet for completeness and 

  all parts for transport damage. 

 

Warning 

Do not use any parts that show evidence of damage!

 

Summary of Contents for 6AT8000-1BA00-5XA0

Page 1: ...02186042 1 23 Preface 1 Scope of Delivery 2 SIPLUS CMS4000 Product Characteristics 3 Industrial I O Node ION PROFIBUS DP SPY T001 Installation and Maintenance 4 6AT8000 1BA00 5XA0 Notes on the CE Mark 5 References 6 Appendix 7 Manual English Release 2009 09 Contact Information 8 ...

Page 2: ...e equipment Qualified persons are defined as persons who are authorized to commission to earth and to tag cir cuits equipment and systems in accordance with established safety practices and standards Intended Use Please note the following Warning This device and its components may only be used for the applications described in the catalog or technical description and only in connection with device...

Page 3: ...ents 7 3 2 1 Hardware 7 3 2 2 Software 7 3 3 Order Numbers 7 3 4 Network Topology 8 3 5 Interfaces 9 3 5 1 Overview of Interfaces 9 3 5 2 IEEE1394a Interfaces 10 3 5 3 Power Supply Interface 11 3 5 4 Fieldbus Interface 12 3 6 Indicators 13 3 7 Technical Data 14 3 8 Block Diagram 16 4 Installation and Maintenance 17 4 1 Types of Installation 17 4 2 Installation 17 4 3 Disassembly 18 4 4 Example of ...

Page 4: ...ument is valid for the following device ION PROFIBUS DP SPY T001 1 3 Audience This document is intended for personnel involved in the commissioning and using of the device ION PROFIBUS DP SPY T001 1 4 Standards and Approvals The device ION PROFIBUS DP SPY T001 meets the requirements of the CE mark Extended information can be found in the appendix of this manual Note The particularized approvals ar...

Page 5: ...pe of Delivery What is shipped Device ION PROFIBUS DP SPY T001 3 pin plug in terminal block PHOENIX CONTACT COMBICON 3 Pin MVSTBW 2 5 3 STF 5 08 2 2 Unpacking and Checking After unpacking please check the packet for completeness and all parts for transport damage Warning Do not use any parts that show evidence of damage ...

Page 6: ... ION PROFIBUS DP SPY T001 captures all of the data which is exchanged in between of any two devices which are present at the attached PROFIBUS DP bus and transmits the measured data to a superior industrial PC via its FireWire IEEE1394a standard link with 400 Mbps The device is designed for the usage on a DIN rail ION PROFIBUS DP SPY T001 ...

Page 7: ...IEEE1394 Ethernet and USB interfaces power supply units and connecting cables depending on the used SIPLUS CMS4000 components 3 2 2 Software CASTOMAT X Tools XP Standard or Professional Edition 3 3 Order Numbers Article Order Number MLFB ION PROFIBUS DP SPY T001 6AT8000 1BA00 5XA0 User Documentation http support automation siemens com X Tools Standard Edition 6AT8000 0AB00 1BA0 X Tools Professiona...

Page 8: ... is equal to the one of a bus with branching but without loops Tree topology The tree topology facilitates the building of networked systems by connecting two further nodes to each node tree topology Chain topology The chain topology enables the building of networked systems by connecting one further node to each node chain topology Caution The maximum number of nodes per bus is limited to 63 The ...

Page 9: ...0 Manual English A5E02186042 9 23 3 5 Interfaces 3 5 1 Overview of Interfaces The device ION PROFIBUS DP SPY T001 provides three plugs for further SIPLUS CMS4000 components and one interface to connect the fieldbus solution PROFIBUS DP ION PROFIBUS DP SPY T001 ...

Page 10: ... English A5E02186042 10 23 3 5 2 IEEE1394a Interfaces At the ION PROFIBUS DP SPY T001 the IEEE1394a Interfaces P1 P2 P3 are implemented as 6 pin sockets IEEE1394a Interfaces Caution Only cables of a maximum length of 4 5 m may be connected to the IEEE1394a Interfaces ...

Page 11: ... 90 seconds the device starts automatically again power supply interface Caution The device ION PROFIBUS DP SPY T001 is designed for operation with safety extra low voltage This means that only safety extra low voltages SELV complying with IEC950 EN60950 VDE0805 can be connected to the power supply terminals The power supply unit for the supply of the ION PROFIBUS DP SPY T001 has to meet NEC Class...

Page 12: ...ROFIBUS DP SPY T001 SIPLUS CMS4000 Manual English A5E02186042 12 23 3 5 4 Fieldbus Interface At the ION PROFIBUS DP SPY T001 the interface of the fieldbus solution PROFIBUS DP is implemented as a SUB D socket fieldbus interface ...

Page 13: ...K Description indicator for the connection to the controller Color yellow Condition off no connection to the controller on connection to the controller established blinks data exchange with the controller Name COM Description data transfer indicator Color green Condition off firmware does not operate on firmware operates Name BUS Description operating mode indicator Color green Condition off no da...

Page 14: ...input Input voltage 18 32 VDC Typ Power loss at 24 VDC 12 W Typ Current consumption at 24 VDC 0 5 A IEEE1394a Interface P1 P3 Number 3 Connector type 6 pin socket Type IEEE1394a interface Transfer speed 400 Mbps Standard IEEE1394a Fieldbus Interface BUS Number 1 Connector type SUB D socket Type PROFIBUS DP interface Transfer speed 9 6 19 2 45 45 93 75 187 5 500 kbps 1 5 3 6 12 Mbps Operation mode ...

Page 15: ...ature during operation 0 55 C Transportation and storage temperature 25 85 C Humidity rating 5 95 not condensing EMC interference emission EN 55011 2007 Class A EMC interference immunity EN 61000 6 2 2005 Degree of protection IP20 Constructive Structure Dimensions H x W x D in mm 200 x 60 2 x 126 5 Design aluminum stainless steel Color silver Weight 1 kg Mounting DIN rail profile DIN EN 50022 35x1...

Page 16: ...FIBUS DP SPY T001 SIPLUS CMS4000 Manual English A5E02186042 16 23 3 8 Block Diagram block diagram PROFIBUS DP Interface FPGA Link Layer Physical Layer FIFO CTRL Logic µC FPGA IEEE1394a Power Supply 24 VDC PROFIBUS DP PROFIBUS DP ...

Page 17: ...the device on the DIN rail and push it down towards the DIN rail so that it snaps in Installation of electric connection cables Install the plug of the PROFIBUS DP connection cable Install the plugs of the IEEE1394 connection cables Install the terminal block of the power supply connection cable installation of the ION PROFIBUS DP SPY T001 on a DIN rail Caution The spaces which are specified in ch...

Page 18: ...les Disassemble the terminal block of the power supply connection cable Disassemble the plugs of the IEEE1394 connection cable Disassemble the plug of the PROFIBUS DP connection cable Removal of the device from the DIN rail Push the device down against the DIN rail and hang it out disassembly of the ION PROFIBUS DP SPY T001 from the DIN rail 1 2 3 ...

Page 19: ... Note This image shows an exemplary installation Technical data subject to change 4 5 Grounding The screw on the front side of the device is provided as grounding connection 4 6 Maintenance If a fault develops please send the device to the Siemens logistics center Address SIEMENS AG I IA RETOUREN CENTER FUERTH SIEMENSSTR 2 90766 FUERTH GERMANY ...

Page 20: ...es as de scribed in this commissioning manual Conformity Certificates The EC Declaration of Conformity is available for the responsible authorities according to the abovementioned EC Directive at the following address SIEMENS AG I IA SE DE WUERZBURGER STR 121 90766 FUERTH GERMANY Notes for the Manufacturers of Machines This product is not a machine in the sense of the EC Machinery Directive There ...

Page 21: ...Industrial I O Node ION PROFIBUS DP SPY T001 SIPLUS CMS4000 Manual English A5E02186042 21 23 6 References 6 1 Other Documentation SIPLUS CMS4000 User Documentation ...

Page 22: ...does not contain complete detail information to the product due to reasons of clarity and can therefore exclude each thinkable case of assembly usage or the maintenance Further information is obtained from your local Siemens office and from the homepage http www siemens de siplus cms Technical data subject to change In cases of doubt the German document is valid ...