Description
9229 9862 176 0D
27
2013-08-28
A further shunt release, transformer-operated release, undervoltage release or
instantaneous release can be installed as a 2nd release.
2nd shunt release (Y2) 3AX1101
Transformer-operated releases (Y4, Y5) 3AX1102, (Y6) 3AX1104
The second shunt release Y2 is installed whenever more
than one shunt release is needed.
In this version, the electrical “open” command is passed
by means of a magnet armature to the “OPEN” latch by
release of an energy storage mechanism, thus opening
the vacuum circuit-breaker. This opening solenoid is not
designed for continuous operation. Any necessary
varistors and rectifiers are integrated in the release.
Power consumption is approximately 60 W / VA
Fig. 34
2. Shunt release (54.2)
The transformer-operated releases Y4, Y5 or Y6 consist
of an energy storage mechanism, an unlatching fixture
and an electromagnetic system. If the tripping current is
exceeded (90 % of the transformer-operated release's
rated current), the energy storage mechanism is
unlatched, thus initiating opening of the vacuum circuit-
breaker.
For use of the transformer-operated release, matching
transformers are also needed for matching, in addition to
the main current transformers.
Power consumption for 0.5 A and 1 A
≤
6 VA at
≤
90 %
of the transformer-operated release's rated current and
with open armature.
Fig. 35
Transformer-operated releases (54.3)
Summary of Contents for 3AH4
Page 4: ...4 9229 9862 176 0D 2013 08 28 Blank page ...
Page 14: ...Transport storage and packing 14 9229 9862 176 0D 2013 08 28 Blank page ...
Page 42: ...Description 42 9229 9862 176 0D 2013 08 28 Blank page ...
Page 52: ...Operation 52 9229 9862 176 0D 2013 08 28 Blank page ...
Page 60: ...Maintenance 60 9229 9862 176 0D 2013 08 28 Blank page ...
Page 62: ...Index of keywords 62 9229 9862 176 0D 2013 08 28 Blank page ...