Maintenance
58
9229 9862 176 0D
2013-08-28
Interrupter service life
If switching operations occur frequently under overload or short circuit, the service
life of the vacuum interrupters may be reached prematurely.
Replace the interrupters after reaching the maximum permitted operating cycle
number of 30,000 mechanical or electrical load setting changes (up to the rated cur-
rent).
When ordering vacuum interrupters, please always state the circuit-breaker type
and serial number (see“Rating plate” on page 33).
Accessories and spare parts
Replacing spare parts
To ensure that the device operates reliably, spare parts must be replaced only by
trained and certified personnel.
Fig. 71
Accessories available for order
Always specify the vacuum circuit-breaker's type and serial no. (see “Rating plate”
on page 33) when ordering spare parts.
CAUTION
Risk of injury!
The vacuum circuit-breaker should be taken out of the switch cabinet or switch-
gear for servicing.
Separate vacuum circuit-breakers from the control feed voltage or switch it off
and release low-voltage plug or clip connection.
Accessory/spare part
Order no.
Comments
Operating instructions
9229 9862 100
Hand crank
3AX1530-2B
Lubricant
see “Maintenance plan” on
page 54, note 3)
Vaseline (contact grease)
e. g. Atlantic white, Atlantic Mineralölwerk GmbH
Pasty consistency, flame point
210 °C, low acid
Summary of Contents for 3AH4
Page 4: ...4 9229 9862 176 0D 2013 08 28 Blank page ...
Page 14: ...Transport storage and packing 14 9229 9862 176 0D 2013 08 28 Blank page ...
Page 42: ...Description 42 9229 9862 176 0D 2013 08 28 Blank page ...
Page 52: ...Operation 52 9229 9862 176 0D 2013 08 28 Blank page ...
Page 60: ...Maintenance 60 9229 9862 176 0D 2013 08 28 Blank page ...
Page 62: ...Index of keywords 62 9229 9862 176 0D 2013 08 28 Blank page ...