8.10.4
Cooling system faults
The following table shows the possible causes of and remedial measures for faults on water-
cooled machines.
Table 8-3
Cooling system faults
↓ Overheating
↓ Water leaking
Possible causes of faults
Remedial measures
X
Reduced cooling
Check the cooling water flow, increase the amount of cooling water if
necessary.
X
Cooling water flow rate too low
Consult the manufacturer. If the specified cooling water quality is ob‐
served, the cooling system is maintenance-free.
X
Inlet temperature too high
Set the correct upstream temperature.
X
Cooling water supply switched off
Switch on the cooling water supply.
X
Cooling water contains too many or unsuit‐
able antifreeze and corrosion-protection
agents
Use cooling water of the agreed quality.
X Leaks in the cooling system
Consult the manufacturer.
X Defective cooling water connection
Find the leak and seal it.
Operation
8.10 faults
SIMOTICS TN Series N-compact 1LH8
90
Operating Instructions 06/2017