7.5
Setpoint values for monitoring the bearing temperature
Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7-1
Set values for monitoring the bearing temperatures before commissioning
Set value
Temperature
Disconnecting during commissioning
120 °C
Normal operation
Measure the normal operating temperature of the bearings T
op
at the installation site in °C. Set
the values for shutdown and warning according to the operating temperature T
op
.
Table 7-2
Set values for monitoring the bearing temperatures in normal operation
Set value
Temperature
Warning in normal operation
T
op
+ 5 K ≤ 115 °C
Disconnection in normal operation
T
op
+ 10 K ≤ 120 °C
See also
Thermal motor protection (Page 26)
7.6
Set values for monitoring the winding temperature
Prior to commissioning
Before running the machine for the first time, set the temperature value for shutdown on the
monitoring device.
Table 7-3
Set values for monitoring the winding temperatures during commissioning
Set value
Temperature
Shutdown
145 °C
Start-up
7.5 Setpoint values for monitoring the bearing temperature
SIMOTICS TN Series N-compact 1LH8
Operating Instructions 06/2017
77
Summary of Contents for 1PQ8
Page 2: ...06 06 2017 10 16 V15 00 ...
Page 92: ...Operation 8 10 faults SIMOTICS TN Series N compact 1LH8 92 Operating Instructions 06 2017 ...
Page 130: ...Service and Support SIMOTICS TN Series N compact 1LH8 130 Operating Instructions 06 2017 ...
Page 134: ...Quality documents SIMOTICS TN Series N compact 1LH8 134 Operating Instructions 06 2017 ...
Page 139: ......