7.15
Shielding at Device Housing
The device provides the opportunity to connect cable shields directly at the device. For
this purpose shield connection clamps by Phoenix are used.
The device is designed for usage with the following shield connection clamps by
Phoenix:
Shield connection clamp
Connection method
Max. tightening
torque
Phoenix article
number
SK 8
Screw connection (M4)
0.6 Nm
3025163
Creating the contact between a cable and the device housing
1. Remove the insulation of the cable in the place the shield connection clamp is to be
fixed.
2. Place the cable between the suitable slot holes at the device.
3. Put the clamp over the cable into the slot holes.
4. Push the clamp to the back so that the lugs lock in the circular holes.
5. Fix the cable using the knurled screw.
85
Drive System SD4S - Hardware Description
Connectors