6.2.2.2
Technical Data
Electrical Specification
NOTICE
Continuous duty (S1) with a load >75 % rated output active power
Consequence: premature aging of the electrolytic capacitors
→ Remedy: mains choke is mandatory (see below)
Device variant
Unit
0SD4SC1E1Cxxxx
Mains supply
Phase conductors
1 AC
Rated mains supply
V
rms
230
110
Input voltage range
V
rms
99 … 253
Mains frequency ±2 %
Hz
50 / 60
Overvoltage category acc. to DIN EN
61800-5-1
III
Supply system types
Symmetrically grounded TN and TT mains
Rated input power
kVA
2.25
1.13
Rated input current
A
rms
9.8
Max. inrush current
A
5.8
Mains choke
(mandatory for continuous duty (S1) with a load >75 % rated output active power)
Rated current
A
10
Inductance
mH
2.9
Article No.
13015834
Protection of the power converters
Fuse
A
16
I²t value diode
A²s
700
Fuse type
5SE1 316
Design
NEOZED D01
Short circuit current rating (SCCR)
A
1000
Line filter acc. to DIN EN 61800-3 (EMC category C3)
Motor cable length ≤5 m
Integrated line filter
Motor cable length >5 m
External line filter necessary
e.g. B84142A0010R000 (TDK & EPCOS Group)
Logic supply
Rated supply voltage (SELV) −15 % +20 %
V
DC
24
Power consumption
A
< 0.5
DC link
Rated voltage DC bus
V
DC
325
155
Capacity of DC link
mF
1.120
Overvoltage threshold
V
DC
410
Discharge time
min
10
Output data (±3 %)
Drive function
Vector control / V/f control / BLDC control
Operating frequency
kHz
8
16
24
32
Rated output current
A
rms
10.0
8.0
7.0
6.0
Peak output current
A
rms
28.0 (2.0 s)
28.0 (2.0 s)
28.0 (1.4 s)
28.0 (1.1 s)
)
A
rms
12.5
10.0
8.7
7.5
45
Drive System SD4S - Hardware Description
Device Variants SD4S