Name
Display
Description
Value
selection
Display
Initial
value
Description
ALM
ALM
Behavior during non-stable
distance measurement
CLP, HLD
cLP
X
If the distance measurement
is not stable, the maximum
current/maximum voltage at
the analog output is issued.
hLd
If the distance measurement
is not stable, the most
recently valid current/voltage
value at the analog output is
maintained.
RST
rSt
Reset to factory settings
NO, YES
no
X
No reset.
YES
Reset all values to factory set‐
tings with the exception of the
PNP/NPN selection.
DSP
dSP
Display settings
ON, OFF
on
X
Display shows display value in
cm.
oFF
Display switches off 30 sec‐
onds after an operating but‐
ton was last pressed.
DLY
dLY
Setting the time functions for
the switching output.
OFF, OFD,
OND, SHT
oFF
X
No time function activated.
oFd
Switch-off delay, adjustable
from 0 … 999 ms.
ond
Switch-on delay, adjustable
from 0 … 999 ms.
Sht
Single shot, adjustable from 0
… 999 ms.
NER
nEr
Distance assignment for 4 mA
or 0.04 V.
0 … 300
0
0
Value range 0 … 300
FAR
FAr
Distance assignment for
20 mA or 10 V.
0 … 300
300
300
Value range 0 … 300
Q_1
q_I
Distance assignment for
switching output Q1.
0 … 300
300
300
Value range 0 … 300
The factory setting of the analog output can be adjusted via the menu items
ner
and
far
:
The
ner
value defines the distance assignment for 4 mA / 0.04 V.
The
far
value defines the distance assignment for 20 mA / 10 V.
20 mA
(10 V)
4 mA
(0,04 V)
Analog output
Sensing
range
too far,
no target
too close
Distance
24 mA
(>11 V)
<2 mA
(0,02 V)
If the switching output is to be set via the menu, adjust entry Q_1.
CONFIGURATION
4