Configuration
Perform configuration:
4.1
Setting the analog output
The analog output is configured as follows at the factory:
4 mA = 0 mm
20 mA = 3,000 mm
For additional settings,
see "Setting the analog output, switching output, and other sen‐
sor configurations via the menu", page 9
.
4.2
Setting the switching output via the teach-in quick access button (-/Q1)
The sensing range is adjusted by pressing the teach-in quick access button for > 1 s.
Do not operate the teach-in buttons using sharp objects. We recommend placing the
sensing range in the object, e.g., see Graphic E. Once the sensing range has been
adjusted, the object is removed from the path of the beam, which causes the back‐
ground to be suppressed and the switching output to change (see Graphic C).
The switching output is adjusted and ready for operation. Refer to Graphic C to check
the function. If the switching output fails to behave in accordance with Graphic C, check
application conditions. See section Fault diagnosis.