16
8027092/AE00/V1-0/2022-10| SICK
O P E R A T I N G I N S T R U C T I O N S | VISIC100SF
Subject to change without notice
6
MENUS
6.4
Menu - Error status
Function: Display current error message
Display
●
Status LED is yellow.
●
The currently pending error is displayed.
●
The malfunction message is acknowledged automatically when the malfunction is
cleared.
6.5
Menu - Measuring Values
Function: Display measured value characteristics and messages
Display
6.6
Menu - Display Parameters
Function: Display and change parameters
●
General and non-safety relevant parameters are stored.
●
The change can be made in operating mode.
Display Parameters
●
Software version
●
Serial number of the adjustment tool
●
Language: Select language
– German (factory setting)
– English
– USA English
– French
– Italian
●
LCD function: Test LCD hardware.
– All LEDs light up for approx. 2 seconds.
– Backlight is yellow.
– All points are displayed on the LED.
Symbol
Description
Function
DP1
Measuring point number
Digital measuring point
CO
Gas type formula
Gas type display
ppm
Unit
51.0 l
Measured value (example)
I = Current measured value (actual value) of the gas
concentration
#
Maintenance information
Gas sensor maintenance required (maintenance date
exceeded)
Comm.Error
Malfunction measuring
point
Communication malfunction, gas sensor
↔
Adjustment tool
Underrange
Monitoring measuring range
Measuring signal < permissible range (< zero point –
6%)
Overrange
Measuring signal > permissible range (> measuring
range end value +6%)
Warm-Up
Time
Warm-up time
Warm-up time of gas sensor active