NOTE
The memory offset for profile entries in the log depends on the number of event entries
(
).
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte N+1...N+M: Profile
entries
Coding
Byte
N+1
Number of implemented profile entries (unsigned integer
8, maximum: 32)
Byte
N+2...N
+3
First implemented profile ID (unsigned integer 16)
The following bytes repeat the coding of the first implemented
profile ID.
7.1.2.2.1.17
Incoming process data valid
Process Data In valid
can be used to read out whether the current incoming process data
of a specific IO-Link port is valid.
This setting can only be called up via the PLC interface.
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 5, bit 0: PDIV
(incoming process data valid)
Coding
0
Incoming process data is invalid
1
Incoming process data is valid
7.1.2.2.1.18
Outgoing process data valid
Process Data Out valid
can be used to read out whether the current outgoing process data
of a specific IO-Link port is valid.
This setting can only be called up via the PLC interface.
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 5, bit 1: PDOV (out‐
going process data valid)
Coding
0
Outgoing process data is invalid
1
Outgoing process data is valid
7.1.2.2.1.19
IO Provider Status Input
This bit indicates the validity of the input data source.
Properties
Value
PROFINET access
SIG200-IO-Link master (slot 2, subslot 1)
Index 0xB200/0xB201/0xB202/0xB203, byte 6, bit 0: IOPSI
Coding
0
Input data source invalid
1
Input data source valid
7.1.2.2.1.20
IO Provider Status Output
This bit indicates the validity of the output data source.
SIG200 CONFIGURATION
7
8017853.1D0S/2021-11-04 | SICK
O P E R A T I N G I N S T R U C T I O N | Sensor Integration Gateway - SIG200