NOTE
The upload of one IODD file takes a few minutes. Depending on the size of the specific
IODD file the upload is faster or slower. It is not unusual in case the IODD upload needs
1-5 minutes or longer untill the IODD is fully visualized in the user interface.
Figure 18:
CONFIGURATION
page, IO-Link ports
The port owner determines who can write process data outputs. This can be set to
either fieldbus, REST or logic editor. When this setting is set to
REST
, no available
process data outputs are displayed on the
LOGIC EDITOR
page.
If the fieldbus is the port owner, the minimum process cycle time is as short as possible
and cannot be changed because the port parameterization comes from the PLC.
The
Data Storage
function can be configured for
Restore
or
Restore
according to
the desired use case. If data storage is to be used,
Expected Device ID
and
Expected Vendor
ID
must be set.
NOTE
If an IO-Link port has been configured, click
Apply
to change the parameterization.
Otherwise, the parameterization will not be sent to the device.
NOTE
If
Fieldbus
(fieldbus) has been configured as the port owner, the parameterization is set
by the PLC and cannot be changed via the user interface. The corresponding control
surfaces are also grayed out in the Maintenance user level.
NOTE
The state of pin 2 is only mapped to the fieldbus processing data when the port owner
is set to
Fieldbus
.
7.3.5.4
IO-Link devices
IODD view
The SIG200 user interface is manufacturer-independent and can be used to connect
and visualize IO-Link devices with connection class A from any manufacturer.
7
SIG200 CONFIGURATION