12
Technical data
12.1
Data sheet
Table 21: Data sheet for the safety system
Performance level
PL d (ISO 13849-1)
Supply voltage V
S
24 V DC (16.8 V DC ... 28.8 V DC) (SELV)
1)
Ambient operating temperature
-10 °C ... +50 °C
Storage temperature
–20 °C ... +50 °C
Air humidity
50 °C, 90% relative humidity (EN 61131-2)
Permissible operating height
≤
2,000 m above sea level
Safe state
The safety-related semiconductor outputs are
in the OFF state (low).
1)
The external supply voltage must jumper a brief power failure of 20 ms as specified in IEC 60204-1. Suit‐
able power supply units are available as accessories from SICK.
12.2
Response time
The response time of the safety system is composed of the following times:
•
Response time of the primary protective device (t
PrimaryProtDev
)
•
Response time of the logic (t
SafetyController
)
•
Response time of the relay(s) (t
Relay
)
The response time of the safety system is determined using the following formula:
t
SafetySystem
= t
PrimaryProtDev
+ t
SafetyController
+ t
Relay
Response time of components
Table 22: Overview of component response times
Components
Part number
Response
time
Primary protective device
deTec4 (resolution 30 mm, length 1,500 mm)
1211506
13 ms
deTec4 (resolution 30 mm, length 1,200 mm)
1211502
12 ms
deTem4 (4 beams, distance between beams
300 mm)
1082692
20 ms
Logic
Flexi Classic main module UE410-MU4T0 (pro‐
gram 7 or 8)
6035243
13 ms
Relay
UE410-2RO4
6032677
30 ms
UE410-4RO4
6032676
30 ms
NOTE
If relays other than those stated above are used, the response time of the relays used
must be taken into account.
TECHNICAL DATA
12
8023421/12KF/2019-01-22 | SICK
O P E R A T I N G I N S T R U C T I O N S | sBot Stop
51
Subject to change without notice