3.4
Functioning of the programmable input
Value
Notes
PNP mode
Deactivated
< 5.0 V
Also deactivated when not connected
Active
> 10.0 V
Max. applied voltage not higher than
UV
NPN mode
Deactivated
> 10.0 V
Max. applied voltage not higher than
UV
Active
< 4.0 V
Also active when not connected
The programmable input must be active for the durations specified below (e.g., U
> 10.0 V in PNP mode ) in order to set the corresponding functions. For a description of
the available functions and how to select them via the menu, see
outputs and other sensor configurations via the menu", page 8
Function
Minimum duration
Maximum duration
Laser shutdown
4 ms
-
External teach-in Q1
External teach-in Q2
4 ms
1 s
1 s
2 s
3.5
Alignment
Align the sensor with the object. Select the position so that the red emitted light beam
hits the center of the object. You must ensure that the optical opening (front screen) of
the sensor is completely clear [F]. We recommend making the adjustments using an
object with a low remission.
Figure: E
4
Configuration
Perform configuration:
4.1
Setting the switching output via the teach-in quick access button (-/Q1) (+/Q2)
(Set/Q3)
The sensing range is adjusted by pressing the teach-in quick access button for > 1 s.
NOTE
The teach-in quick access button (Set/Q3) is only active if the
OUT
option has previously
been selected in the
MF
menu item. See section
for more information
COMMISSIONING
3
8020034.17U4 | SICK
Subject to change without notice
7