5 Installation/Mechanical connection
5.1 Installation on the mounting rail
The PAC50 pressure switch has an integrated fixing mechanism for installing on a mounting rail according to
DIN EN 60715 – 35 mm x 15 mm/7.5 mm.
•
To install the PAC50, position the lower fixing guide on the mounting rail (see Figure 7
1
) and tilt the
PAC50 up until it locks into place (see Figure 7
2
and
3
).
•
To remove the PAC50 from the mounting rail, pull the fixing clip down and tilt the PAC50 up and away from
the mounting rail.
Figure 7: Installation on the mounting rail
5.2 Installation with a switch panel mounting set
To install in a switch panel, use the switch panel mounting set, which is available as an accessory (see
Figure 8). The maximum switch panel thickness is 5 mm. Figure 9 shows the dimensions of the cut-out
section in the switch panel.