Devices with a max. protective field range of 4.0 m and devices with max. protective
field range of 5.5 m:
•
40 ms: Full protective field range, increased availability in dusty conditions, for
example
•
30 ms: Smaller protective field range with shorter response time
Devices with a max. protective field range of 9.0 m:
•
50 ms: Full protective field range, increased availability in dusty conditions, for
example
•
40 ms: Smaller protective field range with shorter response time
b
Select scan cycle time.
✓
The resulting response time and the range of the fields are shown.
Additional interference protection
If you mount several safety laser scanners in close proximity to each other, this can
lead to mutual interference. You will prevent mutual interference in neighboring safety
laser scanners if you choose different settings for interference protection.
Modes 1 to 4 are available. Interference protection influences the scan cycle time and
therefore the response time.
•
Mode 1 = + 0 ms per scan cycle
•
Mode 2 = + 1 ms per scan cycle
•
Mode 3 = + 2 ms per scan cycle
•
Mode 4 = + 3 ms per scan cycle
b
Configure a different mode for each safety laser scanner that is mounted in close
proximity.
✓
The resulting response time is shown.
Complementary information
NOTE
The response time of the safety laser scanner depends on the scan cycle time, interfer‐
ence protection, and multiple sampling,
see "Response times", page 186
. In addition
to the response time of the safety laser scanner, further signal transmission and
processing also influence the time until the end of the dangerous state.