![SICK Flow-X Operating Instructions Manual Download Page 43](http://html.mh-extra.com/html/sick/flow-x/flow-x_operating-instructions-manual_1264313043.webp)
43
8015675/1EEU/2021-12| SICK
O P E R A TI N G I N S T R UC TI O N S | Flow-X
Subject to change without notice
APPENDIX
7
7.3
Flow
-
X/M I/O specifications
7.3.1
I/O signal specifications
Signal
Num
-
ber
Type
Description
Analog input
6
[1]
4 … 20 mA,
0 … 20 mA,
0 … 5 V,
or 1 … 5 V
Analog transmitter input
High precision (error <0.008 % FS, resolution 24 bit)
For (for example) 3xdP, P, T.
The inputs are potential-free (optically isolated).
Temperature input
2
PRT
Analog Pt100 input.–220 … +220 °C for 100 Ω
input.
Resolution 0.02 °C
Max. error:
0 … +50 °C: 0.05 °C
–220 … +220 °C: 0.5 °C
Hart modems
4
[1]
HART
Loop inputs for HART transmitters, in addition to the
first 4 analog input signals.
Analog output
4
4 … 20 mA,
0 … 20 mA,
or 1 … 5 V
Analog output for PID, pressure control valve. 12
bits A DC, 0.075 % FS. Update cycle 0.1 s.
[1]
Total number of analog HART inputs = 6.
Table 13:
Analog signal specifications
Signal
Num
-
ber
Type
Description
Dual pulse input
1
[1]
High impedance High speed USM counter input, pulse counting.
Trigger level 0.5 V. Max. level 30 V. Frequency range
0 ... 5 kHz (4 x dual pulse) or 0 ... 10 kHz (4 x single
pulse).
Compliant with ISO6551, IP252 and API 5.5.
True Level A implementation.
Digital input
16
[1]
High impedance Digital status input, or test inputs. Update cycle
0.5 ms for 2 inputs, for others 250 ms max.
Digital output
16
[1]
Open Collector
Update cycle for relays etc. (0.5 A DC). Rated output
100 V, @24 V. Update rate at cycle time.
Test output
1
[1]
Open Collector
Two contiguous pulse outputs, for test applications.
One output corresponds to the highest value of the
dual pulse inputs and the other output corresponds
to the difference between the dual input pulses. The
outputs are On-Off-HighZ.
Pulse output
4
[1]
Open Collector
Max. 500 Hz
[1]
Total number of digital digital o pulse density
measured value inputs = 16.
Table 14:
Digital specifications
Signal
Number Type
Description
Serial
2
RS485/422/
232
Serial multipurpose communication interface
Minimum 110 baud, maximum 256000 baud
Ethernet
2
RJ45
100 Mbit/s
Ethernet interface - TCP/IP
Table 15: Communication specifications