Operating Instructions
Fault diagnosis
Chapter
5
A3M60 Basic
Tab. 16: Contents of the
diagnostics message
WARNING
5.3.3
IO message in case of an error
If, in case of a serious error, a correct position calculation cannot be ensured, the output of
the position within the process data is blocked and instead an error code output. These
manufacturer-specific error codes are outside the valid value range and permit a detailed
error analysis.
Error code
Diagnostics message in octet 3
Description
Dec Hex
–
12 FF.FF.FF.F4
Memory error 38h
Forbidden parameter in the
µC<Flash
–
11 FF.FF.FF.F5
Position error 36h
Erroneous communication with
FRAM (Wiegand IC)
–
10 FF.FF.FF.F6
Position error 36h
Synchronization error on shut
down
–
8 FF.FF.FF.F8
Position error 36h
Synchronization error on switch on
–
5 FF.FF.FF.FB
Position error 36h
Analog signals out of tolerance
(vector length)
–
4 FF.FF.FF.FC
Position error 36h
Memory error 38h
Erroneous communication with
EEPROM
–
3 FF.FF.FF.FD
Position error 36h
Analog signals out of tolerance
(amplitude)
–
16 FF.FF.FF.F0
Position and/or memory error Occurrence of several errors
simultaneously
Evaluate bit 31 of the input data using your control system to detect serious errors!
If, in the case of serious error, it cannot be ensured the position output is correct, this
situation is indicated by setting the most significant bit 31. The position value is then
outside the valid range and can be identified as clearly erroneous (see section 5.3.2
on page 22).