Use and Maintenance Manual ATS LOGICA CONTROL PANEL with ATS115
WARNING:
Every control panel is produced and configured for operations at: 400V
– 50
Hz.
Control panels between 45 and 125A have the following voltage and frequency values:
DC voltage:
12Vdc.
AC voltage:
400Vac.
(The ABB contactors coils can work at 100÷250V.)
Frequency:
1) 50Hz.
2) 60Hz.
It is possible change the frequency values by modifying a parameter on the ATS115 controller (SW).
Control panels between 160 and 4000A have the following voltage and frequency values:
DC voltage switch.
The Control Panels are suitable for operating at different genset battery voltages:
1) 12Vdc.
2) 24Vdc.
It is possible change this level by modifying the Hardware on the control panel internal wiring (see
par. 4.2).
AC voltage switch.
The Control Panels are suitable for operating at different AC voltages:
3) 220Vac.
4) 380Vac.
5) 400Vac.
6) 440Vac.
In order to adjust the Control Panel to the different AC voltage level, it is necessary to carry out some
operations related to both control panel internal connections (HW) and ATS115 controller
parameters modifications (SW).