Use and Maintenance Manual ATS LOGICA CONTROL PANEL with ATS115
The
VOLTAGE SWITCH
is carried out in the “
X1
” bar and in the “
TR1
” autotransformer for
160÷4000A capacities.
X1
TR1
On “X1” bar and on “TR1” the connected cables are
identified by
3 red rings
.
ENSURE THAT THE CABLES WITH THE RED RINGS ARE PLACED AS REPORTED IN THE
ELECTRICAL DIAGRAM SPECIFICATIONS.
ENSURE THAT THE CABLES WITH THE RED RINGS ARE PLACED AS REPORTED BELOW
AND SEE THE ELECTRICAL DIAGRAM SPECIFICATIONS FOR THE IDENTIFICATION OF THE
NUMBER OF CABLES.
OPERATING VOLTAGE: 220V (MOVE THE RED RINGED CABLE ONLY)
-X1- -TR1-
220V
220V
Right
Left
Side by side
NOTE
: for the side by side “X1” bar, the red ringed cable is connected to the terminals with an “
odd
number
” (
left
).
WARNING:
it is advisable to move one cable at a time in order to avoid inverting the sequence with
the other cables.
CHECK THE VOLTAGE ON THE SWITCH AND POWER SUPPLY CONNECTORS (OPTIONAL).