Use and Maintenance Manual ATS LOGICA CONTROL PANEL with ATS115
The insertion of the CTs on the Load line allows to measure also the power supplied by the mains.
For the CTs characteristics, see the indications on the ATS115 controller manual. The CT primary
current has to be at least equal to the nominal current
In
of the plant.
The CTs installation includes the board kit and possible fastening as shown in the figure below.
The parameters to configure on the controller are:
P.0302 = CT primary current
P.0303 = 2
– On Load
P.0310 = 5
– CT secondary current
REAR