Use and Maintenance Manual ATS LOGICA CONTROL PANEL with ATS115
After the control panel is configured
with the correct voltage value, supply the “
XR
” and “
XG
” bar with
the operating voltage in order to check.
The voltage on the “
XM-1
” and “
XM-2
” bar and on the “”
KBG
” switch supply connector (
ABB
), or
with “
KR
” and “
KG
” must be
230V
.
Disconnect the voltage and put the supply connectors again at their place:
OPERATING VOLTAGE: 380/400/440V (move the red ringed cable only)
-X1- -TR1- -TR1- -TR1-
380/400/440V 380V 400V 440V
Right
Left
Side by side
NOTE: for the side by side “X1” bar, the red ringed cable is connected to the terminals with an “
even
number
” (
right
).
WARNING:
it is advisable to move one cable at a time in order to avoid inverting the sequence with
the other cables.
“KR-KG”
“KBG”
ABB
“KBG”
TECHNOELECTRIC