Use and Maintenance Manual ATS LOGICA CONTROL PANEL with ATS115

 

 

SICES is pleased to thank you for purchasing our ATS LOGICA Automatic Transfer Switch Panel. 
This  Control  Panel  is  the  result  of  the  design,  the  selection  of  the  best  components,  the  careful 
assembly and the strict test to which all SICES products are submitted. 
We  would  like  to  recommend  to  read  this  manual  carefully,  to  observe  the  safety  rules  and  all 
regulations  for  the  correct  use  and  maintenance  of  the  ATS  LOGICA  Control  Panel.  This  will 
guarantee you better duration results and efficiency. 
For any doubts or questions, please do not hesitate to contact our technicians for clarifications. 
 
The  information  contained  in  this  manual  are  updated  to  the  printing  stage,  but  they  may  still  be 
modified without  notice in compliance with our aims of continuous development and improving of 
products. 
 
This manual and all the enclosed documents are to be intended as part of the Control Panel and are 
intended to be read by all persons are involved in the life cycle of the machinery. Therefore they 
must be collected in a well-known place and be accessible to the operators, keeping them carefully 
in order to avoid their loss and/or deterioration. 
 
This  manual  has  been  drafted  for  the  installer,  the  user  and  the  maintenance  technician.  It  is 
compulsory to read it carefully and examine all electrical diagrams and instructions enclosed, as they 
provide indications on the Control Panel use and they also show the technical characteristics as well 
as the installation and assembling features. 
 
 

The Customer must complies with all the safety instructions. 

 

 

WARNING: 
The  automatic  transfer  switch  control  panel  must  be  only  used  by  properly 
trained personnel. 
The installation must only be planned and carried out by skilled personnel. 
Any fault in installation and use may cause serious damage to the machinery, 
to the user system and to the persons involved. 

 

Please note that it is compulsory to observe all regulations in force in the country of 
installation. In case of more regulations in force on the same matter, always consider 
the strictest ones.

 

 

 

WARNING: 
400V 

– 50 Hz.

 

 
 
 
 
 
 
 

Summary of Contents for ATS LOGICA

Page 1: ...Filename Use and Maintenance Manual Rev 01 Date 01 03 2016 Product ATS LOGICA Control Panel Model with ATS115...

Page 2: ...rlocked contactors 16 4 5 2 Switch carried out by motorized changeover switch 17 4 5 3 Power cables interconnections and how to tighten the screws 20 4 5 4 AUTO Operating mode 22 4 5 5 MANUAL Operatin...

Page 3: ...intended to be read by all persons are involved in the life cycle of the machinery Therefore they must be collected in a well known place and be accessible to the operators keeping them carefully in...

Page 4: ...ted considering that no other heating sources occur nearby If the control panel is placed into a room together with other panels a suitable distance must be guaranteed in order to allow the dissipatio...

Page 5: ...h the plant values in detail check power voltage current and frequency For the electric connection strictly follow the enclosed electric diagram it contains useful information In the connection of pow...

Page 6: ...Genset ATS Control Panel and or plant connected to it In order to protect the panel from indirect contact overload and short circuit it is the installer s responsibility to connect a protection device...

Page 7: ...nels between 160 and 4000A have the following voltage and frequency values DC voltage switch The Control Panels are suitable for operating at different genset battery voltages 1 12Vdc 2 24Vdc It is po...

Page 8: ...s to the RB wire clamp 1 Battery Voltage 12Vdc wire 2 7B to wire clamp 12 2 Battery Voltage 24Vdc wire 2 7B to wire clamp 24 Example of 24Vdc operation For the HW change see the attached document in t...

Page 9: ...to modify the operating voltage The sticker on the control panel rear door identifies the internal equipment BEFORE CHANGING THE VOLTAGE Disconnect the supply of the following devices KBG capacity 160...

Page 10: ...NS ENSURE THAT THE CABLES WITH THE RED RINGS ARE PLACED AS REPORTED BELOW AND SEE THE ELECTRICAL DIAGRAM SPECIFICATIONS FOR THE IDENTIFICATION OF THE NUMBER OF CABLES OPERATING VOLTAGE 220V MOVE THE R...

Page 11: ...with KR and KG must be 230V Disconnect the voltage and put the supply connectors again at their place OPERATING VOLTAGE 380 400 440V move the red ringed cable only X1 TR1 TR1 TR1 380 400 440V 380V 400...

Page 12: ...nual ATS LOGICA CONTROL PANEL with ATS115 OFF AUTO MAN Set the parameters by means of the configuration keyboard Arrow keys for the navigation and CONFIGURATION Area Buttons for the modes Arrow keys f...

Page 13: ...ce Manual ATS LOGICA CONTROL PANEL with ATS115 OFF AUTO MAN Area Using the arrow keys put the device on CONFIGURATION Area Using the arrow keys select the page 03 PROGRAM Using the arrow keys select t...

Page 14: ...ple indicates the parameter P 0102 The square brackets flash to indicate that the value can be changed Using the arrow keys define the new value and confirm with ENTER the square brackets stop flashin...

Page 15: ...r to change the parameters by the controller keyboard 1 Operating voltage 220V a P 0102 220 b P 0202 220 2 Operating voltage 380V a P 0102 380 b P 0202 380 3 Operating voltage 400V a P 0102 400 b P 02...

Page 16: ...lly interlocked 45 125A 2 1 motorized four pole changeover switch 160 4000A Mechanical interlock Auxiliary contacts 45 125A 45 125A The contactors are interlocked by means of a proper accessory In ord...

Page 17: ...rized changeover switch 160 4000A there is a mechanical indicator that shows the status of the main contacts Therefore it is possible to understand on which source the load is inserted The figure belo...

Page 18: ...rce B GENSET phases before supplying the LOAD The inverse cyclic sense can cause serious damages to the system Source A Source B Source A Source B Source A Source B WITH INDICATOR ON 0 ZERO THE LOAD I...

Page 19: ...of the manual command With lock inserted the supply is stopped inhibiting the electrical command The changeover switch thanks to its exclusive mechanical structure can be activated manually by a prop...

Page 20: ...connection of the power cables Source A MAINS Source B GENSET is carried out directly on the contactors terminals sizes 45 125A the operation brings to the disconnection of the auxiliary circuits cab...

Page 21: ...BF50 65 BF80 OTM160 OTM250 OTM400 OTM600 OTM800 OTM1000 OTM1600 OTM2000 OTM2500 CS6 M4 M5 M6 M8 M10 M12 M12 M12 M14 1 Nm 3 9 Nm 5 Nm 22 Nm 44 Nm 75 Nm 75 Nm 75 Nm 70 Nm WARNING Before connecting phas...

Page 22: ...SOURCE B GENSET the contact N O closes on terminals XM 110 and 111 After the Source B Genset is started the voltage created is acknowledged by the ATS115 controller Then it commands the status switch...

Page 23: ...of the Genset and that the Genset is connected with right voltage With supply on SOURCE B GENSET press BCB once in order to switch the Load on 0 with supply on SOURCE A MAINS press ACB once in order t...

Page 24: ...ith ATS115 CARPENTRY 45 125A Interface terminal board Earthing bar Auxiliary circuit area Power circuit area Connection power cables XR Source A MAINS front Connection power cables XL LOAD XG SOURCE B...

Page 25: ...TRY 160 800A Terminal board interface Earthing bar Auxiliary circuits Power circuit area Connection bars power cables XR Source A MAINS front Connection bars power cables XL LOAD XG SOURCE B GENSET Co...

Page 26: ...1000 2500A REAR Terminal board interface Connection bars power cables XR Source A MAINS front Connection bars power cables XL LOAD rear Interface cables return duct Earthing bar Auxiliary circuits Pow...

Page 27: ...RY 3150 4000A Interface terminal board Connection bars power cables XR Source A MAINS front Connection bars power cables XL LOAD rear Interface cables return duct Earthing bar Auxiliary circuits Power...

Page 28: ...ion provided with respect to the operating voltage switch Keep the ATS115 key pressed to move it on OFF WARNING in order to avoid the cables whiplash and the switch damage in case of court circuit it...

Page 29: ...29 Use and Maintenance Manual ATS LOGICA CONTROL PANEL with ATS115 ABB changeover switch Source A Source B...

Page 30: ...the arrow represents the signal direction Panel System 1 Supply 24Vdc from the engine battery 2 Supply single phase available a Voltage 220V 60Hz 220V 60Hz b Voltage 380V 60Hz 220V 60Hz c Voltage 440...

Page 31: ...age level 12Vdc 24Vdc no bridge Configuration of the battery charger as supply Configuration of the rapid charge Configuration of the type of battery see manual attached Output 12 24Vdc Fault contact...

Page 32: ...both batteries positive power supply must be connected as follows Batt Batt Source A Source B XM L L XM L A L B B XM L F1 D1 OPT B The wire currently connected to the terminal XM L by the fuse F1 mus...

Page 33: ...tery voltage To manage the Source A as Genset you must configure the following parameters P 0100 1 P 0113 0 0 P 0115 60 0 P 0118 999 0 P 0304 0 No P 2001 4004 P 2002 1 0 P 2003 Source A stop P 3005 10...

Page 34: ...haracteristics see the indications on the ATS115 controller manual The CT primary current has to be at least equal to the nominal current In of the plant The CTs installation includes the board kit an...

Page 35: ...disconnecting the panel from all external sources of energy PAY ATTENTION IN CASE OF EQUIPMENT WITH AUTOMATIC OR REMOTE STARTING SYSTEM AUTOSTART MISSING MAINS SENSING DISPOSAL PROGRAMMABLE FUNCTION...

Page 36: ...f there is any damage caused by transport and check to make sure that the details indicated on the identification label correspond to what was requested If the panel is not installed immediately but s...

Page 37: ...lose nor on Mains or on Genset Source A Mains not live Source B Genset stopped Protection fuse burned Replace the fuse The remote command of the switch is not allowed Check the electric continuity of...

Page 38: ...ic alarm off twice for the acknowledgement With alarm acknowledged and still live the visual signalling keeps on flashing Remove the cause of the alarm If the alarm is of a Warning type it is not nece...

Page 39: ...ou have already identified the component considered faulty it is useful to refer the written you find in it The warranty conditions are indicated in the document GENERAL CONDITION OF SALE and it is re...

Page 40: ...45 600 400 200 21 70 600 400 200 21 100 600 400 200 25 125 600 400 200 25 160 1000 600 250 56 250 1000 600 250 56 400 1000 600 300 60 630 1000 600 400 90 800 1000 600 400 100 1000 1900 800 600 245 125...

Page 41: ...s r l reserves the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liabilit...