Aqua Timer Plus
-
12/34
Advance
0 d L
0 d L 1
Management of the start of the regeneration in the case of inhibit.
See par. 6.12
Program
1 d L
1 d L 0
FLAG not used
Program
2 d L
2 d L 0
FLAG not used
Program
3 d L
3 d L 0
FLAG not used
Program
Fast flashing of the display. The programming is stored in eeprom.
6.2.1.c – List of codes to be programmed
For the programming and the meaning of the codes see par. 6.3. In this modality the programming of the following
codes is recommended:
Tab. 9 – Table of the codes in one single column modality LLL1 – LL–1
Code
Meaning
SC02
Regeneration starting time and interval days between two regenerations programming
SC03
Regeneration cycle steps programming
SC05
End of cycle impulse duration and dosing pump divider programming
SC00
Initialisation of the system
6.2.2 – LLL1 – LL–2 – One single column with start by volume.
6.2.2.a – Operative characteristics.
In this operative modality the regeneration starts exclusively when the volume reaches the value 0.
The flag
0HL
allows to enable the regeneration start by time. In fact, the immediate start of the cycle by finished
volume remains the same, to which the start of the cycle at the programmed time after the interval days programmed or
on the active days, is added.
The control on the
reserve
is not available.
The control on the
remote start
is available, which can start up the regeneration both immediately and deferred to the
programmed time, based on the content of the flag
2HL
.
In this operative modality it is not possible to activate the cycle with the
stand-by
.