Aqua Timer Plus

 - 

                                                                                                                                      

23/34 

 

 

 

Code 

visualised 

 

Display

 

Meaning

 

S C 0 3

 

PROGRAM 

1 C 1 0

 

Programming of the regeneration cycle times. 

With the key 

Program 

the next phase is accessed 

S C 0 4

 

PROGRAM 

- - - 0

 

Programming of the litre counter divider.  

This value indicates the type of litre counter divider: 

0

 =free litre counter divider, 

= litre counter divider pre-programmed. 

This programming acts directly on the flag 

0CL

PROGRAM 

x x x x 

 

If the free litre counter divider has been chosen, a value of between 

0

 and 

899

 impulses / litre may be set. 

 

1 4.0 1 

If  the  pre-programmed  litre  counter  divider  has  been  chosen,  one  of  the 

values suggested in tab. 24,

 

par. 6.6 may be programmed.  

S C 0 5

 

PROGRAM 

x x x x 

 

Programming of the duration in minutes and seconds of the end of cycle 

impulse, from 

0

 to 

59

 minutes and

 59

 seconds. 

PROGRAM 

x x x x 

 

Divider of the dosing pump, programmable from 

to 

9999

 impulses / litre.  

S C 0 6

 

PROGRAM 

x x x x 

 

Programming  of  the  volume  of  resin  in  the  cylinder:  the  value  can  vary 

from 

to 

9999

 litres. 

PROGRAM 

H H 5 0

 

Programming of the percentage of the total volume total of treatable water 

which must be held in reserve. 

PROGRAM 

C H 5.0

 

Programming of the value of capacity of exchange of the resin; the value 

can vary from 

1.4 

to

 9.0

.

  

S C 0 7

 

PROGRAM 

x x x x 

 

Programming

 

of the code of access to the programming functions. Using 

the key 

Advance

, any value from 

to 

9999 

may be set

 

S C 0 8

 

PROGRAM 

x.x.x x 

 

Allows  the  total  counter  of  the  volume  consumed  to  be  visualised.  This 

cannot be modified, but only visualised. Since it is composed of 8 digits, it 

is visualised in two parts;  

These are the 4 higher numbers.  

PROGRAM 

x x x.x. 

These are the 4 lower numbers.  

S C 0 9

 

PROGRAM 

S C - - 

Allows access to the general programming and to the setting of the flags as 

already described in the previous paragraphs. 

 

 

 

6.4 – Programming of the reserve 

 

Aqua Timer Plus

 allows for the volume of water treatable to be controlled, comparing it to a possible value of 

reserve, 

but only working in the 

single column

 modality with 

mixed 

control for the start of the regeneration. The percentage of 

reserve is programmed using the code 

SC02

 and expresses the 

percentage of the total volume available 

which must 

be held in reserve. In this way, if there are 25,000 treatable litres available and 30% of reserve is required, the value 

HH30

 must be programmed in the code 

SC02

 and the code 

SC00

 must be keyed in to have the calculations on the 

volume  carried  out.  When  the  volume  reaches  the  value  7,500,  a  regeneration  which 

will  be  carried  out  at  the 

programmed time 

will be set

 

N.B.!! 

The  control  of  the  reserve  is  active  only  in  the  “one  single  column”  modality  with  mixed  control  for  the 

regeneration. 

  

Summary of Contents for Aqua Timer Plus

Page 1: ...1 34 USE AND MAINTENANCE MANUAL AQUA TIMER PLUS y Distributed b 37 Tannery Lane 06 08 Tannery House Singapore 347790 Tel 65 6741 2994 Fax 65 6741 2995 S I A T A Asia Pacific Pte Ltd Distributed by ww...

Page 2: ...oltage 73 23 CEE 93 68 CEE The fulfilment of the following regulations has been verified EN 50081 1 General Regulation on Emissions part 1 residential commercial and light industry environment EN 5008...

Page 3: ...volume start 20 6 3 PROGRAMMING CODES 22 6 3 1 Access to the programming codes 22 6 3 2 List of programming codes and their meaning 22 6 4 PROGRAMMING OF THE RESERVE 23 6 5 REMOTE START 24 6 6 PROGRAM...

Page 4: ...ion in progress or to jump one or more phases by pressing the key Regener during the stop phase Aqua Timer Plus makes it possible to use an outlet which is activated during the second phase of the reg...

Page 5: ...10 Network frequency 50 Hz 3 Power absorbed 30 VA Operative temperature 0 C 55 C Class of protection IP65 Protection from disturbances ICE 65 Trial class 4 3000 V Reading scale 0 999 999 Litri Box di...

Page 6: ...on mixed control time volume for the regen Tab 2 Functionality of the keys Key Description CODE Access to the programming of the work parameters through the protection code During the programming retu...

Page 7: ...box with a label identifying the product carrying the following infrormation name of producer and PN producer AT PLUS2 05 the quick reference guide for the installation and programming may be found in...

Page 8: ...h free contact outlets with the following signals Dosing pump End of cycle impulse Impulse during phase 2 Alarm Regeneration in progress Warning Before carrying out any installation and or maintenance...

Page 9: ...ing the service The programming will be carried out via the keypad on the front of the controller Aqua Timer Plus has the following operative modalities Tab 4 Table of the operative modalities Code De...

Page 10: ...Code 0 0 0 0 Key in the protection code programmed with the function SC07 Advance 0 0 0 2 Key the code on the display with the keys Advance and Code Code S C State of access to the keying in of the p...

Page 11: ...0 9 By pressing Advance key the programming code is increased up to 9 Program L L L 1 Single column modality If necessary modify the data with Advance Program L L 1 Regeneration by time If necessary m...

Page 12: ...eps programming SC05 End of cycle impulse duration and dosing pump divider programming SC00 Initialisation of the system 6 2 2 LLL1 LL 2 One single column with start by volume 6 2 2 a Operative charac...

Page 13: ...FLAG not used Program 2 H L 2 H L 0 Immediate start of the regeneration at the command of the remote start See par 6 5 Advance 2 H L 2 H L 1 Start of the regeneration at the time programmed at the com...

Page 14: ...the regeneration cycle stop times SC04 Programming of the litre counter divider prescaler SC05 Programming of the duration of the end of cycle impulse and of the litre counter divider of the dosing pu...

Page 15: ...days of the week programmed Program 2 H L 2 H L 0 Immediate start of the regeneration at the command of the remote start See par 6 5 Advance 2 H L 2 H L 1 Start of the regeneration at the programmed...

Page 16: ...on the volume or on the reserve Control is available on the remote start which can start up the regeneration both immediately and deferred to the programmed time on the basis of the content of the fl...

Page 17: ...Management of the start of the regeneration in the case of inhibit See par 6 12 Program 1 d L 1 d L 0 FLAG not used Program 2 d L 2 d L 0 FLAG not used Program 3 d L 3 d L 0 FLAG not used Program Fast...

Page 18: ...rt by volume FLAG Display Operative state Data visualised Program S C State access to the selection of the programming codes Advance S C 0 9 With the key Advance the programming code is increased up t...

Page 19: ...unter divider prescaler SC05 Programming of the duration of the end of cycle impulse and of the litre counter divider of the dosing pump SC06 Programming of the volume of resin of the percentage of re...

Page 20: ...controller will immediately position the cam in the stand by position that is it will carry out the exchange of the columns The regeneration will start from the stand by position The control on the re...

Page 21: ...not used Program 2 d L 2 d L 0 FLAG not used Program 3 d L 3 d L 0 FLAG not used Program Fast flashing of the display The programming is memorised in eeprom 6 2 6 c List of codes to be programmed For...

Page 22: ...visualises the new value Causes any regeneration in progress to end immediately S C 0 1 PROGRAM d H x x Programming of the hardness value of the water from 1 to 99 The hardness value must be expresse...

Page 23: ...9 0 S C 0 7 PROGRAM x x x x Programming of the code of access to the programming functions Using the key Advance any value from 0 to 9999 may be set S C 0 8 PROGRAM x x x x Allows the total counter of...

Page 24: ...atio between the number of impulses read by Aqua Timer Plus and the unit of load in transit in the counter used litres or m Aqua Timer Plus has two work modes free prescaler if the flag 0CP is equal t...

Page 25: ...ed prescaler the volume calculated is optimised by returning to zero the digits which are not decreased and by rounding it off Example If the volume calculated is 15 435 litres and the prescaler is pr...

Page 26: ...rotation time of the first phase must therefore be of 50 seconds 25 dedicated to reaching the position of stand by and 25 to reach the position expected for the first phase The movement time between...

Page 27: ...Time diagram of the standard regeneration cycle and cam with stand by Type 2 Pos of stand by 1C 2C 3C 4C Search of the stroke end Stop Stop Stop Stop Stroke end Stroke end Movement phase of 25 second...

Page 28: ...unters and turn off the led SALT When the number of regenerations which can be carried out reaches the value dd00 one last regeneration is available after which Aqua Timer Plus is blocked with the led...

Page 29: ...f the columns The connections shown in the table must be respected rigorously to avoid damaging the sensor In the second case there are only two wires between which there is a closure for each impulse...

Page 30: ...e clock has passed the time programmed for the start of the cycle the regeneration will not be able to start until the conditions are repeated that is after 24 hours To avoid waiting for 24 hours with...

Page 31: ...ua Timer Plus at 230 Vac AT PLUS2 05 this fuse must be of delayed 0 5A 7 2 the motors of the distributors do not stop 1 Check that the run end wires of the distributors marked 96 S are correctly inser...

Page 32: ...Aqua Timer Plus 32 34 Appendix A General electrical connections CE0027...

Page 33: ...Aqua Timer Plus 33 34 Appendix B Electrical connections for the single distributor CE0028...

Page 34: ...dix C Electrical connections for the duplex distributor CE0021 Distributed by 37 Tannery Lane 06 08 Tannery House Singapore 347790 Tel 65 6741 2994 Fax 65 6741 2995 S I A T A Asia Pacific Pte Ltd Dist...