background image

INSTALLATION

WIRE SPLICING

Splice wire to motor leads. Use only copper wire for connections to
pump motor and control box.

1. 

Taped splice (Wire Sizes No. 

8

 (7mm

2

) and larger):

A. Cut off motor leads. Stagger lead and wire length so that 2nd

lead is 2" (50.

8

mm) longer than 1st lead and 3rd lead is 2"

(50.

8

mm) longer than second.

B. Cut off power supply wire ends. Match colors and lengths of

wires to colors and lengths of motor leads.

C. Trim insulation back 1/2" (12.7mm) from supply wire and

motor lead ends.

D. Insert motor lead ends and supply wire ends into butt con-

nectors (see Fig. 2). Match wire colors between supply wires
and motor leads.

E. Using crimping pliers, indent butt connector lugs (see Fig. 3)

to attach wires.

F. Cut “Scotchfil” electrical insulation putty into 3 equal parts

and form tightly around butt connectors. Be sure scotchfil
overlaps insulated part of wire.

G. Using #33 Scotch tape, wrap each joint tightly; cover wire for

about 1-1/2" (3

8

.1mm) on each side of joint. Make four pass-

es with the tape. When finished you should have four layers
of tape tightly wrapped around the wire. Press edges of tape
firmly down against the wire (see Fig. 5).

NOTICE:

Since tightly wound tape is the only means of keep-

ing water out of splice, efficiency of splice will depend on care
used in wrapping tape.

NOTICE:

For wire sizes larger than No. 

8

 (7mm

2

), use sol-

dered joint rather than Scotchfil putty (see Fig. 4).

2.

Heat shrink splice (For wire sizes #14, 12 and 10 AWG (2, 3 and

5mm

2

):

A. Remove 3/

8

" (9.5mm) insulation from ends of motor leads

and power supply wires.

B. Put plastic heat shrink tubing over motor leads between

power supply and motor.

C.

Match 

wire colors and lengths between power supply and

motor.

D. Insert supply wire and lead ends into butt connector and

crimp (See Figs. 2 and 3). 

Match 

wire colors between power

supply and motor. Pull leads to check connections.

E. Center tubing over butt connector and apply heat evenly with

torch (match or lighter will not supply enough heat).

NOTICE: 

Keep torch moving. Too much concentrated heat

may damage tubing (see Fig. 6).

3.

Mechanical Splice Kit with plastic insulators (for 14, 12 and 10
Gauge AWG Wire (2, 3 and 5mm

2

):

A. Cut off motor leads. Stagger lead and wire length so that 2nd

lead is 4" (101.6mm) longer than 1st lead and 3rd lead is 4"
(101.6mm) longer than second.

B. Cut off wire ends. 

Match 

colors and lengths of wires between

power supply and motor.

C. Trim insulation back 1/2" (12.7mm) from power supply wire

and motor lead ends.

D. Unscrew plastic caps from insulators. Place a cap and neo-

prene gasket sleeve on each wire to be spliced (see Fig. 7).

E. Slide insulator body onto one wire end (Fig. 7).

F. Insert wire end into butt connector and crimp. 

Match 

wire col-

ors between power supply and motor (see Fig. 

8

).

G. Center insulator body over splice and slide gasket sleeves

into body as far as they will go. Screw caps onto insulator
body (Fig. 9) and tighten by hand for a strong, waterproof
splice.

POWER SUPPLY WIRE INSTALLATION

1. To test submersible, momentarily (no more than 30 seconds)

connect it to proper power supply. Power supply frequency and
voltage must match motor nameplate frequency and voltage to
within ±10%.

2. Fasten power supply wire leads securely to pump discharge sec-

tion; leave 4-5" (100-125mm) of slack in leads at this point.
Securely fasten leads to plastic pipe within 6" (150mm) of the
pump discharge section. Use centering guides to protect wire
and pipe from rubbing well casing.

3. Connect copper ground wire to motor bracket. Ground wire

must be as large as wires supplying current to motor. Consult
current Canadian Electrical Code and local codes for grounding
information.

4

1/2"

(12.7mm)

Butt connector

Insulator body

centered over splice

 

End cap

Gasket

Insulator body

Figure 

8

 – Wire ends spliced

Figure 9 – Tighten end caps

Gasket sleeve in place

Cap screwed on

1"

2

1"

2

Butt connector or

crimp or solder

12.7mm  12.7mm

Indent here

Alternate method
twist and solder

Completed splice

Connector

Heat shrink tubing

Figure 2

Figure 3

Figure 4

Figure 5

Figure 6

Figure 7 – Ready to splice

Figure 8 – Wire ends spliced

Figure 9 – Tighten end caps

Summary of Contents for SD-A200

Page 1: ...SATION Pompe submersible de 4 po à deux et trois fils de 1 2 à 1 1 2 CV 60 Hz MANUAL DEL USUARIO Bombas Sumergibles de 4 de dos y tres alambres de 1 2 a 1 1 2 hp 60 Hz CONSUMER HOT LINE 1 800 535 4950 Monday Friday 7 AM to 5 PM EST SD A300 SD A301 SD A302 SD A314 SD A3183 SD A3184 SD A3065 SD A3067 SD A3207 SD A31015 SD A30610 SD A200 SD A201 SD A202 SD A203 SD A214 ...

Page 2: ...ivery damage Report any damage immediately to shipping carrier or to your dealer Well driller should thoroughly develop well pump out all fine sand and foreign matter before pump is installed See Initial Startup Pump performance is based on pumping clear cold water with no entrained air Warranty is void in the following conditions Pump has pumped excessive sand which can cause premature wear to pu...

Page 3: ...re Green Control box is not required See Figure 1B for correct hook up information for 230 Volt 2 Wire motors only Fig 1B Single phase 2 Wire Connections Follow color coding when connecting control box Yellow to Y Red to R Black to B 3 NOTE 1 Maximum wire lengths shown maintain motor voltage at 95 of service entrance voltage running at maximum nameplate amperes If service entrance voltage will be ...

Page 4: ...er will not supply enough heat NOTICE Keep torch moving Too much concentrated heat may damage tubing see Fig 6 3 Mechanical Splice Kit with plastic insulators for 14 12 and 10 Gauge AWG Wire 2 3 and 5mm2 A Cut off motor leads Stagger lead and wire length so that 2nd lead is 4 101 6mm longer than 1st lead and 3rd lead is 4 101 6mm longer than second B Cut off wire ends Match colors and lengths of w...

Page 5: ...eal or pitless adapter unit well unit electri cal conduit and surface piping Installation must meet all code requirements that apply CONNECTING TO TANK WATER SYSTEM Hazardous pressure Submersible pumps can develop very high pressure in some situations To prevent tank blowup install a pressure relief valve able to pass full pump flow at 75 PSI 517 1kPa when using an air over water pressure tank Ins...

Page 6: ...le Union Submersible motor control 3 wire models Electrical disconnect Pressure gauge Air volume control Pressure switch To house service Gate valve Relief valve 2 ft 6m See table Figure 11 Typical Pre Charge Tank Installation Figure 12 Typical Standard Tank Installation CUT IN CUT OFF Pre charge Tank PSI kPa PSI kPa PSI kPa 20 137 9 40 275 8 18 124 2 30 206 8 50 344 7 28 193 1 40 275 8 60 413 7 3...

Page 7: ... nameplate or on circuit Use only control box designed for use with pump rating diagram inside control box cover Wire size too small Check wire size against chart Page 3 Install correct wire size Pump starts too frequently Leaks in system Check all tank connections with soapsuds for air leaks System must be air and water tight Check plumbing for leaks Pressure switch Check for defective switch or ...

Page 8: ...misapplication tampering alteration nor due to improper installation operation maintenance or storage nor to other than normal application use or service including but not limited to operational fail ures caused by corrosion rust or other foreign materi als in the system or operation at pressures in excess of recommended maximums Requests for service under this warranty shall be made by returning ...

Page 9: ...rteur ou au dis tributeur L aménagement du puits doit être entièrement terminé avant de procéder à l installation de la pompe extraire par pompage toutes les particules de sable fin et les impuretés Voir Démarrage initial Le rendement de la pompe est évalué en fonction d un pompage d eau claire et froide sans entraînement d air La garantie est annulée dans les circonstances suivantes La pompe a ex...

Page 10: ...s d alimentation en courant rouge noir et un conducteur de terre vert Une boîte de commande n est pas requise Voir la Figure 1B concernant les informations du bon branchement des moteurs de 230 volts à 2 conducteurs seulement 10 REMARQUE 1 Les longueurs maximum de câblage assurent une tension moteur représentant 95 de la tension de service admise en fonctionnement maximum selon le nombre d ampères...

Page 11: ...our nissent pas assez de chaleur REMARQUE Déplacer constamment la flamme du chalumeau Une concentration excessive de la flamme risque d endommager le gainage voir Fig 6 3 Kit de raccordement mécanique avec isolants en plastique pour types de fils AWG de calibre 14 12 et 10 2 3 et 5 mm2 A Sectionner les fils conducteurs du moteur Échelonner la longueur des conducteurs et des fils électriques de la ...

Page 12: ... le robinet vanne en vue de son installation définitive près du réservoir voir Fig 11 et 12 10 Monter le plombage sanitaire du puits ou l ensemble adaptateur sans cavité le puits la canalisation électrique et la tuyauterie en surface L installation doit satisfaire à tous les codes et réglementations qui s appliquent CONNEXION AU RÉSERVOIR CIRCUIT D EAU Pression dangereuse Les pompes submersibles p...

Page 13: ... 124 2 18 206 8 30 344 7 50 193 1 28 275 8 40 413 7 60 262 38 DISTANCE SÉPARANT LE CLAPET DE LA PRISE DE PURGE SUPÉRIEURE VOLUME DU RÉSERVOIR LITRES DISTANCE EN m pi gallons U S 159 42 0 6 2 310 4 82 0 9 3 454 2 120 1 5 5 832 7 220 1 5 5 1192 3 315 3 10 1987 1 525 4 6 15 Couvercle de puits ventilé Boîte de com mande 3 types de câblage Sectionneur de courant Réservoir à pression préchargée Manocont...

Page 14: ...e schéma du circuit couvercle de la boîte commande conçue spécialement pour cette pompe de commande Calibre de fil trop mince Comparer le calibre du fil avec le tableau de la page 10 Installer le fil du type qui convient La pompe démarre trop fréquemment Présence de fuites dans le circuit Contrôler les connexions des tuyaux du réservoir en utilisant de Le circuit doit être étanche à l air et à l e...

Page 15: ...s ou entretenus correctement ni à ceux qui n ont pas été utilisés ou entretenus normalement y compris mais sans s y limiter aux produits ayant des pannes de fonctionnement causées par la corrosion la rouille ou autre corps étranger dans le système ou à des produits ayant fonctionné à des pressions dépassant la limite maximale recommandée Les demandes de service en vertu de la présente garantie ser...

Page 16: ...fectamente el pozo bombearlo hasta extraer toda la arena fina y materiales extraños antes de que se instale la bomba Véase Puesta en Marcha Inicial Los valores de rendimiento de la bomba se basan en el bombeo de agua limpia y fría sin arrastre de aire La garantía es nula en las siguientes condiciones La bomba ha bombeado un exceso de arena que puede causar el des gaste prematuro de la bomba Véase ...

Page 17: ...nductores tienen dos conductores de alimentación Rojo Negro y un conductor de tierra Verde No se requiere una caja de control Ver Figura 1B para la información de conexión correcta de los motores de dos conductores de 230 Voltios solamente Figura 1B Conexiones de los motores de dos conductores monofásicos Cuando conecte la caja de control siga las siñas de color Amarillo para Y Rojo para R Negro p...

Page 18: ...que calor en forma pareja con un soplete un fósforo o un encendedor no dan suficiente calor AVISO Mantenga el soplete en movimiento Un exceso de calor concen trado puede dañar el tubo de plástico véase fig 6 3 Empalme mecánico con aisladores plásticos para alambre calibre 14 12 y 10 AWG 2 3 y 5 mm2 A Corte los conductores del motor Escalone las longitudes de estos conductores y el alambre de maner...

Page 19: ...tire la válvula de cortina para su instalación permanente cerca del tanque véanse las figs 11 y 12 10 Instale un sello sanitario para pozo o una unidad adaptadora la unidad del pozo los conductos para cables eléctricos y las tuberías de superficie La instalación debe respetar todas las exigencias de los códigos que sean procedentes CONEXIÓN AL TANQUE SISTEMA DE AGUA Presión peligrosa En determinad...

Page 20: ...4 2 30 206 8 50 344 7 28 193 1 40 275 8 60 413 7 38 262 DISTANCIA DE LA VÁLVULA DE RETENCIÓN AL ORIFICIO DE PURGA SUPERIOR CAPACIDAD DEL DISTANCIA en PIES m TANQUE en GALONES l 42 159 2 0 6 82 310 4 3 0 9 120 454 2 5 1 5 220 832 7 5 1 5 315 1192 3 10 3 525 1987 1 15 4 6 Tapa ventilada de pozo Caja de control modelos de 3 alambres Desconector eléctrico Tanque de presión precargado Interruptor de pr...

Page 21: ...n la bomba en el interior sobre la tapa de la caja de control El diámetro de los conductores es Verifique el diámetro de los conductores en el cuadro de la página 17 Instale alambrado de diámetro correcto demasiado pequeño La bomba arranca con demasiada frecuencia Hay pérdidas en el sistema Verifique todas las conexiones del tanque con solución jabonosa para El sistema debe estar herméticamente se...

Page 22: ...traindicadas manejo indebido alteraciones ni debido a instalación funcionamiento mantenimien to o almacenaje incorrectos ni a ninguna otra cosa que no sea su aplicación uso o servicio normales in cluyendo pero no limitado a fallas operacionales cau sadas por corrosión oxidación u otros elementos extra ños en el sistema o funcionamiento a presión por enci ma del máximo recomendado Los pedidos de se...

Page 23: ...23 ...

Reviews: