38
Character
Setting Item, Function, Setting Range
Factory Default
Output OFF time when EVT3 output ON
0 sec.
• Sets Output OFF time when EVT3 output is ON.
If ON time and OFF time are set, EVT3 output can be turned ON/OFF
in a configured cycle when EVT3 output is turned ON.( Fig 7.5-2, p.40)
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT3 type].
• Not available for P control action
• Setting range: 0 to 10000 sec.
EVT3 ORP input error alarm EVT
type
No action
• Selects EVT
output type (except EVT3 type) in order to assess
EVT3 ORP input error alarm.
• Available only when
(ORP input error alarm output) is
selected in [EVT3 type]
•
: EVT1 action
: EVT2 action
: No action
: EVT4 action
EVT3 ORP input error alarm span
when EVT
output ON
0 mV
• Sets span to assess EVT3 ORP input error alarm when EVT
output
(selected in [EVT3 ORP input error alarm EVT
type]) is ON.
• Available only when
(ORP input error alarm output) is
selected in [EVT3 type]
• Setting range: 0 to 2000 mV
When set to 0 (zero), ORP input error alarm is disabled.
EVT3 ORP input error alarm time
when EVT
output ON
0 sec.
• Sets time to assess EVT3 ORP input error alarm when EVT
output
(selected in [EVT3 ORP input error alarm EVT
type]) is ON.
• Available only when
(ORP input error alarm output) is
selected in [EVT3 type]
• Setting range: 0 to 10000 seconds or minutes
(*)
When set to 0 (zero), ORP input error alarm is disabled.
(*) Time unit follows the selection in [ORP input error alarm time unit].