25
Character
Setting Item, Function, Setting Range
Factory Default
EVT1 OFF delay time
0 sec.
• Sets EVT1 delay time.
The EVT1 output does not turn OFF after the input value exceeds the
EVT1 value until the time set in [EVT1 OFF delay time] elapses.
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Not available for the P control action.
• Setting range: 0 to 10000 sec.
EVT1 proportional cycle
30 sec.
• Sets EVT1 proportional cycle.
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Not available for the ON/OFF control action.
• Setting range: 1 to 300 sec.
EVT1 output high limit
100%
• Sets EVT1 output high limit value.
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Not available for the ON/OFF control action.
• Setting range: EVT1 output low limit to 100%
EVT1 output low limit
0%
• Sets EVT1 output low limit value.
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Not available for the ON/OFF control action.
• Setting range: 0% to EVT1 output high limit
Output ON time when EVT1 output ON
0 sec
• Sets Output ON time when EVT1 output is ON.
If ON time and OFF time are set, EVT1 output can be turned ON/OFF
in a configured cycle when EVT1 output is turned ON.(Fig. 7.3-2, p.28)
• Available when
(ORP input low limit action) or
(ORP input high limit action) is selected in [EVT1 type].
• Not available for P control action