![Shimadzu OMRON CJ Series Network Connection Manual Download Page 13](http://html1.mh-extra.com/html/shimadzu/omron-cj-series/omron-cj-series_network-connection-manual_1256907013.webp)
6
.
Serial Communications Settings
10
UPX/UPY/UW/UX series applicable connector: D-SUB 25-pin female
Use
Pin No.
Terminal
name
Function
RS-232C
1
FG
Protective ground or
earth
2
TXD
Data output
3
RXD
Data input
4
RTS
Internal connection to
CTS
5
CTS
Internal connection to
RTS
6
DSR
Handshake (receive)
7
SG
Signal ground
8 to 19
Undefined
-
20
DTR
Handshake (send)
21 to 25 Undefined
-
Cable and pin layout
Serial Communications Unit
(CJ1W-SCU42)
UPX/UPY/UW/UX series
RS-232C
Interface
Signal
name
Pin No.
Pin No.
Signal
name
RS-232C
Interface
FG
1
1
FG
SD
2
2
TXD
RD
3
3
RXD
RS
4
4
RTS
CS
5
5
CTS
5V
6
6
DSR
DR
7
7
SG
ER
8
8 to 19
Undefined
SG
9
20
DTR
FG
Shell
21 to 25
Undefined
D-SUB 9-pin
cable connector: male
D-SUB 25-pin
cable connector: male