- 8 -

4-6. Supplementary explanation of screens 

(1) 0-1 Control Output Screen

• During manual control an output value is set on this

screen.  In automatic control, it is only for monitoring.

• For switching automatic control to manual, press the

key on the control output screen. 

• The MAN monitor LED flashes during manual control and

goes out when control is changed to auto.

• This screen is only for monitoring in the stop mode, when

AT is ON, or keylock is set at 2 or 3.

• Manual control output is released if the stop mode is

selected or the type of input or the measuring range is
changed during manual control.

• For changing the manual output value, the        and

keys are used.  It is not necessary to press the        key.

• During manual control, the setting range of control output

is between 0 and 100%.  In case an output limiter has been
set, that value serves as the higher/lower limit of the
setting range. 

• In ON/OFF action (P=0), manual control output should be

at 0% or 100% (For V and I output, lower limit output
limiter or higher limit output limiter). 

• When auto is changed to manual, the action becomes

balanceless and bumpless.  If the measured value (PV) is
out of the proportional band, it does not attain balanceless
and bumpless action. 

• If power is turned off during manual control output and is

turned on again, the condition is stored in the memory.

(2) 0-2  Control Execution/Stop Screen 

• Use the        and        keys to select control execution

(EXEC) or stop (STBY).  Then register it by means of the

key. 

• Upon selecting stop, the STBY monitor LED turns on and

the control output display turns to 0%. 

• Upon selecting execution, the mode changes to automatic

control; it is not possible to go directly from the stop to the
manual mode. When control is being executed, the STBY
monitor LED remains unlit.

• Even at stop, the alarm works.
• When AT is ON or 1, 2 or 3 of keylock has been selected,

no change is allowed. 

(3) 1-6  Manual Reset Value Setting Screen 

• In the PID operation, an offset is corrected automatically

by I, i.e., integral calculation.  When I is set at OFF, this
correction is not made and output is manually increased or
decreased for correction. This is called manual reset (MR). 

(4) 1-11  Proportional Cycle Setting Screen

• In the case of contact output or SSR drive voltage output,

time in which output is ON + time in which it is OFF in
the proportional band, that is, proportional cycle time is
set. 

(5) 1-12, 1-13  Lower Limit and Higher Limit Output Limiters 

Setting Screens
• The output limiters function effectively to maintain the

lowest  temperature, to suppress control overshoot by
limiting control output to minimum and maximum values
set. 

• In the output limiters, priority is given to the lower limit

value. Therefore, when the lower limit is set at a value
higher than the higher limit value, the higher limit value is
forced to be the lower limit value + 1%.  Therefore, the
higher limit value cannot be set to be less than the lower
limit value + 1%. 

ENT

Note:

Moving to another screen while maintaining the manual
mode is possible.  In this case, it should be noted that
control output is made manually.  The apparatus is in the
manual mode when the MAN monitor LED is flashing.

ENT

(6) 1-14  Soft Start Time Setting Screen 

• Soft start is the function selected to raise control output

gradually in the beginning of control.  It is effective in
preventing excessive current from flowing into a heater or
similar apparatus.

• Soft start functions in the following cases:

Upon applying power in the auto mode
When control stop (STBY) is changed to control 

execution (EXEC)

When scale-over is restored to the normal state (in auto
mode) 

The above are on condition that soft start time and
proportional band are not set at OFF.

• In the following cases, the soft start function is released.

Soft start time has elapsed without problem.
Auto is changed to stop or manual mode during the
execution of soft start.
Soft start time or proportional band is changed to OFF
during the execution of soft start.
The measurement range code is changed during the
execution of soft start. 
Control output characteristic is changed during the
execution of soft start. 
Scale-over of a measured value occurs during the
execution of soft start.
Control output falls to a level below the output value of
soft start during the execution of soft start.

• Auto tuning is unable to be carried out during the

execution of soft start.

5.  Operation

5-1. Setting of set value (SV)

(1) Press the        or        key to set set value.  Keep pressing it to

flash the point of the least digit of set value and increase (or
decrease) value.

(2) After confirming the value to coincide the set value, press

to register the data.

(3) After registration of the data, the point of the least digit goes

off.
Example: Setting set value to 500 °C.

5-2. AT (Auto tuning)

(1) Execution of AT action 

• By pressing the        or        key on AT action control

screen,            display on lower row turns into        and the
point of the least digit starts flashing, then the LED for AT
monitoring turns on to indicate AT standby.  Press
key to start AT action with point going off and LED for
AT monitoring flashing.

• When AT is carried out, ON/OFF action of output is

repeated several times, with the set value as the border
line, to make PID values stored in the memory and
terminates.  At the same time, control is started by using
stored PID constants.
The AT monitor LED goes out and the display on the AT
action control screen changes to            

ENT

key

ENT

key

key

0-0 basic screen

continuing

point flashing

point flashing

one by one

point goes off to 
indicate registration

key

key

ENT

key

0-0 basic screen

point goes off to 
indicate registration

0-1 
AT action control screen 

• LED for AT 

monitoring 
turns on

• LED for AT 

monitoring starts 
flashing 

AT 
action

Starting

point flashing

MAN

ENT

Summary of Contents for SR73A Series

Page 1: ...o the instrument On the terminal nameplate affixed to the case of your instrument the mark is printed This is to warn you of the risk of electrical shock which may result if the charger is touched while it is energized A means to allow the power to be turned off such as a switch or a breaker should be installed in the external power circuit to be connected to the power terminal of the instrument F...

Page 2: ... 14 8 Specifications 15 4 1 Introduction 1 1 Check before use This product has been fully checked for quality assurance prior to shipment Nevertheless you are requested to make sure that there is no error damage or shortage of delivered items by confirming the model codes and checking the external view of the product and the number of accessories Confirmation of Model Codes Check the model codes s...

Page 3: ...th 48 height 91 6 width 44 6 Dimension of current transformer CT for heater break alarm For 0 30A CTL 6 S For 0 50A CTL 12 S36 8 unit mm 2 5 Wiring 1 Wiring operation should be done according to the instruction for the terminal arrangement in section 2 6 Exercise care that no wrong connection is made 2 Crimp terminal should accommodate the M3 5 screw and should have a width of less than 7mm 3 For ...

Page 4: ...nitor LED green On selection by ON turns on AT waiting key flashes on AT execution 3 AH alarm output monitor LED red Turns on for higher limit alarm output ON 4 AL HB alarm output monitor LED red Turns on for lower alarm output ON or heater break alarm ON 5 MAN manual control output monitor LED green Flashes when control output is in manual operation 6 STBY control output stop monitor LED green Tu...

Page 5: ... decimal point in the rightmost position on the top row flashes Press the or key to change the lower limit value and press the key to register the data Upon registering the lower limit value data the decimal point in the rightmost digit in the bottom row begins to flash Change the higher limit value by pressing the or key and register it by means of the key Upon registering the higher limit value ...

Page 6: ...ualoperation 0 100 Themeasuredvalue PV isdisplayedonthetopandthecontroloutput valueonthebottom PressingtheMANkeyonthisscreenswitches autotomanualandviceversa RefertoItem4 6 1 fordetail Control execution stop selecting screen Initialvalue EXEC Settingrange EXEC STBY Execution orstop ofcontrolisselected RefertoItem4 6 2 fordetail AT auto tuning action control screen Initialvalue OFF Settingrange OFF...

Page 7: ...ockissetonlockNo 1 2or3 noselectioncanbeperformedevenifthedigitpointis flashing Digits and arenotshownincaseofnooption Digitsof and arenotdisplayed Measuring range code select digit Initialvalue Multi05 Voltage V 81 Current95fixed Selectingtwodigitsfrom 4 5 Measuringrangecodetable Control output characteristic select digit Initialvalue RA heatingcharacteristics DA coolingcharacteristics RefertoIte...

Page 8: ...the higher limit value is forced to be the lower limit value 1 Therefore the higher limit value cannot be set to be less than the lower limit value 1 ENT Note Moving to another screen while maintaining the manual mode is possible In this case it should be noted that control output is made manually The apparatus is in the manual mode when the MAN monitor LED is flashing ENT 6 1 14 Soft Start Time S...

Page 9: ...m option is added and the lower limit alarm of the alarm type select digit on the function selecting screen of the mode 2 group screen group is selected Lower limit deviation value alarm is output for measured value to be less than set value alarm set value For lower limit deviation value alarm if set value alarm set value is less than the lower limit of the measuring range the action point is low...

Page 10: ...nd 74A series two types of communication interface RS 422A and RS 485 are available Each enables a personal computer or the like to set and read various data by the use of signals which conform with EIA standards RS 422A and RS 485 are communication standards established by the Electric Industries Association EIA which are meant for electrical or mechanical matters the so called hardware but not f...

Page 11: ...ront panel turns on and the commands for read and write through communication become valid Front key operation works only to change from remote to local 7 3 2 Communication address setting screen RS 422A and RS 485 allow connection of a plurality of apparatuses but in fact communication is carried out between two apparatuses Therefore the address of each apparatus is designated by a number between...

Page 12: ... value including a code is less than six characters 0 is inserted between the code and the figure or figures to make the value six characters When a code is excluded each of the 5 characters is a figure or a decimal point Examples of numerical data 1 Command The text format of read data contains only of a command of two characters Command Contents of Read Data PV value Execution SV value 1 Control...

Page 13: ...No did not match The end character was not CR 0DH A hardware error such as a framing error overrun or a parity error occurred 7 5 5 Restrictions by commands etc 1 Restrictions by Read Command Upon receiving the D1 read command the status of unequipped options AH AL HB SB become 0 30H 2 Restrictions by Write Command In the case of P OFF and Y and P output write data of E2 write command of manual ou...

Page 14: ...xt Data 3AH BCC CR 0DH Higher position Lower position Higher position Lower position Received data Transmitted data D1 D1 STBY MAN AH AL AT SB 0 30H or 1 31H PV value SV value Output value Received data Transmitted data D2 D2 Set value of AH Set value of AL Received data Transmitted data D3 D3 CT current value Set value of HB Received data Transmitted data D4 D4 Set value of SB Received data Trans...

Page 15: ... Sampling cycle 0 5 sec PV bias range 200 unit PV filter 0 100 sec 0 without filter Control Control mode Auto tuning PID ON OFF control Proportional band P Off 0 1 999 9 FS Off setting On Off action Integral time I Off 1 6000 sec Off setting P PD action Derivative time D Off 1 3600 sec Off setting P PI action Manual reset MR 50 0 50 0 Valid when P OFF and I OFF Output limiter Lower limit limiter 0...

Page 16: ...tact type or the SSR drive voltage type Alarm action Heater amperage detected by externally attached CT except 0 5V DC input Alarm output On upon detection of heater break while control output is On Current setting range Off 0 1 50 0A Alarm action stops when Off is set or Off 1 500A when 0 5 V DC for CT input is selected Setting resolution 0 1A or 1A Amperage display 0 0 55 0A or 0 550A Display ac...

Reviews: