- 4 -

SR74A

2-7. Terminal arrangement table

3.  Instruction for front panel

3-1.  Drawing and the name of the parts

This is an example of the front panel of SR73A.

Name of parts

: Measured value

(PV) display

: Set value (SV)

display

: Monitor LED
: Key switches

10

20

23

24

19

18

17

16

15

14

13

12

22

21

11

9

8

7

6

5

4

3

2

1

422A

485

RD–

RD+

SD–

SD+

+

SG

SG

L

N

COM+

NC

COM

AL/HR

AH

NO   –

Power

CONTROL
OUTPUT

ALARM
OUTPUT

CT

SB

IN PUT

RTD

TC•mV

V•mA

+A

–B

B

~

Heater break alarm (option) CT input terminal

Name of terminal and description

Terminal number

SR73A and 74A

Power terminal
100-260V  AC

±

10%  50/60Hz  12VA

Protective conductor terminal (        )

Input terminal
R. T. D.  A, Thermocouple, Voltage, C
R. T. D.  B, Thermocouple, Voltage, Current –
R. T. D.  B

Output terminal
Contact: COM, SSR Drive voltage, Voltage, 

C

Contact: NO, SSR Drive voltage, Voltage, 

Current –

Contact: NC

Communication terminal
 For RS-422A

 For RS-485

SG

SG

SD+

+

SD–

RD+
RD–

Alarm output (option) terminal
COM

Contact rating 240V  AC 1.5A 
(resistive load)

AH

Higher limit alarm

AL/HB Lower limit alarm or heater break alarm

Set value bias (option) input terminal

11-12

13

21-22

23-24

7
8

10

18

19
20

1
2
3
4
5

14

15

16

Note:

For Thermocouple, Voltage, and Current input,
measurement error results by connection between B and
B terminal.

3-2.  Instruction for front panel

: Measured value (PV) display (green)

(1) Displays current measured value on the mode 0 basic

screen.

(2) Displays parameter type on each parameter screen.

: Set value (SV) display (orange)

(1) Displays set value on the mode 0 basic screen.
(2) Displays selected item and set value on each parameter

screen.

: Monitor LED

(1) OUT (output) monitor LED (green)

• For contact or SSR drive voltage output, a light turns

on for output ON and turns off for output OFF.

• For current or voltage output, the light intensity

changes proportionally to the output altitude.

(2) AT (auto tuning) monitor LED (green)

• On selection by            , ON turns on AT waiting 

(        key), flashes on AT execution.

(3) AH alarm output monitor LED (red)

• Turns on for higher limit alarm output ON.

(4) AL/HB alarm output monitor LED (red)

• Turns on for lower alarm output ON or heater break

alarm ON.

(5) MAN (manual control output) monitor LED (green)

• Flashes when control output is in manual operation. 

(6) STBY (control output stop) monitor LED (green) 

• Turns on when the control output stop mode is

selected. 

(7) COM (communication) monitor LED (green)

• Turns on when the remote communication mode is

selected.

:  Key switches

(1)

(parameter) key

• Press on set screen to move to next set screen.
• Keep pressing three (3) seconds for function of move

key between basic screen of the mode 0 screen group
and direct call screen of mode 1 screen group.

(2)

(down) key

• Press on the set screen to flash the point of the least

digit and to reduce data or back increment data.

(3)

(up) key

• Press on the set screen to flash the point of the least

digit and to increase data of increment data.

(4)

(entry/registration) key

• Press on the set screen of the mode 0 screen group

and mode 1 screen group to fix the data changed by
the      ,       keys and to extinguish flash of the point.

• The function selecting screen, of the mode 2 screen

group, registers data of the point flashing digit and
simultaneously shifts a data changeable digit (the
point flashing digit). 

• The input scaling screen, of the mode 2 screen group,

registers data and shifts a parameter capable of being
set (in the row in which the rightmost point is
flashing).

• Press the key for five seconds and it functions to

change the basic screen of the mode 0 screen group to
the function selecting screen of the mode 2 screen
group and vice versa.

(5)

(manual) key

• Pressing this key on the control output screen changes

automatic control output to manual control output and
vice versa.  During manual control output, the MAN
monitor LED flashes.

• The        key does not function in the control output

stop mode. 

ENT

MAN

ENT

MAN

PV

SV

OUT

AT

AH

MAN

STBY

COM

AH/HB

SHIMADEN

ENT

MAN

˚C

4

3

2

1

Summary of Contents for SR73A Series

Page 1: ...o the instrument On the terminal nameplate affixed to the case of your instrument the mark is printed This is to warn you of the risk of electrical shock which may result if the charger is touched while it is energized A means to allow the power to be turned off such as a switch or a breaker should be installed in the external power circuit to be connected to the power terminal of the instrument F...

Page 2: ... 14 8 Specifications 15 4 1 Introduction 1 1 Check before use This product has been fully checked for quality assurance prior to shipment Nevertheless you are requested to make sure that there is no error damage or shortage of delivered items by confirming the model codes and checking the external view of the product and the number of accessories Confirmation of Model Codes Check the model codes s...

Page 3: ...th 48 height 91 6 width 44 6 Dimension of current transformer CT for heater break alarm For 0 30A CTL 6 S For 0 50A CTL 12 S36 8 unit mm 2 5 Wiring 1 Wiring operation should be done according to the instruction for the terminal arrangement in section 2 6 Exercise care that no wrong connection is made 2 Crimp terminal should accommodate the M3 5 screw and should have a width of less than 7mm 3 For ...

Page 4: ...nitor LED green On selection by ON turns on AT waiting key flashes on AT execution 3 AH alarm output monitor LED red Turns on for higher limit alarm output ON 4 AL HB alarm output monitor LED red Turns on for lower alarm output ON or heater break alarm ON 5 MAN manual control output monitor LED green Flashes when control output is in manual operation 6 STBY control output stop monitor LED green Tu...

Page 5: ... decimal point in the rightmost position on the top row flashes Press the or key to change the lower limit value and press the key to register the data Upon registering the lower limit value data the decimal point in the rightmost digit in the bottom row begins to flash Change the higher limit value by pressing the or key and register it by means of the key Upon registering the higher limit value ...

Page 6: ...ualoperation 0 100 Themeasuredvalue PV isdisplayedonthetopandthecontroloutput valueonthebottom PressingtheMANkeyonthisscreenswitches autotomanualandviceversa RefertoItem4 6 1 fordetail Control execution stop selecting screen Initialvalue EXEC Settingrange EXEC STBY Execution orstop ofcontrolisselected RefertoItem4 6 2 fordetail AT auto tuning action control screen Initialvalue OFF Settingrange OFF...

Page 7: ...ockissetonlockNo 1 2or3 noselectioncanbeperformedevenifthedigitpointis flashing Digits and arenotshownincaseofnooption Digitsof and arenotdisplayed Measuring range code select digit Initialvalue Multi05 Voltage V 81 Current95fixed Selectingtwodigitsfrom 4 5 Measuringrangecodetable Control output characteristic select digit Initialvalue RA heatingcharacteristics DA coolingcharacteristics RefertoIte...

Page 8: ...the higher limit value is forced to be the lower limit value 1 Therefore the higher limit value cannot be set to be less than the lower limit value 1 ENT Note Moving to another screen while maintaining the manual mode is possible In this case it should be noted that control output is made manually The apparatus is in the manual mode when the MAN monitor LED is flashing ENT 6 1 14 Soft Start Time S...

Page 9: ...m option is added and the lower limit alarm of the alarm type select digit on the function selecting screen of the mode 2 group screen group is selected Lower limit deviation value alarm is output for measured value to be less than set value alarm set value For lower limit deviation value alarm if set value alarm set value is less than the lower limit of the measuring range the action point is low...

Page 10: ...nd 74A series two types of communication interface RS 422A and RS 485 are available Each enables a personal computer or the like to set and read various data by the use of signals which conform with EIA standards RS 422A and RS 485 are communication standards established by the Electric Industries Association EIA which are meant for electrical or mechanical matters the so called hardware but not f...

Page 11: ...ront panel turns on and the commands for read and write through communication become valid Front key operation works only to change from remote to local 7 3 2 Communication address setting screen RS 422A and RS 485 allow connection of a plurality of apparatuses but in fact communication is carried out between two apparatuses Therefore the address of each apparatus is designated by a number between...

Page 12: ... value including a code is less than six characters 0 is inserted between the code and the figure or figures to make the value six characters When a code is excluded each of the 5 characters is a figure or a decimal point Examples of numerical data 1 Command The text format of read data contains only of a command of two characters Command Contents of Read Data PV value Execution SV value 1 Control...

Page 13: ...No did not match The end character was not CR 0DH A hardware error such as a framing error overrun or a parity error occurred 7 5 5 Restrictions by commands etc 1 Restrictions by Read Command Upon receiving the D1 read command the status of unequipped options AH AL HB SB become 0 30H 2 Restrictions by Write Command In the case of P OFF and Y and P output write data of E2 write command of manual ou...

Page 14: ...xt Data 3AH BCC CR 0DH Higher position Lower position Higher position Lower position Received data Transmitted data D1 D1 STBY MAN AH AL AT SB 0 30H or 1 31H PV value SV value Output value Received data Transmitted data D2 D2 Set value of AH Set value of AL Received data Transmitted data D3 D3 CT current value Set value of HB Received data Transmitted data D4 D4 Set value of SB Received data Trans...

Page 15: ... Sampling cycle 0 5 sec PV bias range 200 unit PV filter 0 100 sec 0 without filter Control Control mode Auto tuning PID ON OFF control Proportional band P Off 0 1 999 9 FS Off setting On Off action Integral time I Off 1 6000 sec Off setting P PD action Derivative time D Off 1 3600 sec Off setting P PI action Manual reset MR 50 0 50 0 Valid when P OFF and I OFF Output limiter Lower limit limiter 0...

Page 16: ...tact type or the SSR drive voltage type Alarm action Heater amperage detected by externally attached CT except 0 5V DC input Alarm output On upon detection of heater break while control output is On Current setting range Off 0 1 50 0A Alarm action stops when Off is set or Off 1 500A when 0 5 V DC for CT input is selected Setting resolution 0 1A or 1A Amperage display 0 0 55 0A or 0 550A Display ac...