Example: Mark state

× 

D+ > T 

× 

D-

Space state

× 

D+ < T 

× 

D-

7-2-3. Connection of RS-485 

(1) The logical levels of input and output of this apparatus are

basically as follows: 
Mark state

-Terminal < +Terminal 

(including the state in which communication is not carried
out)
Space state 

-Terminal > +Terminal 

However, since the impedance of +terminal and -terminal of
this apparatus is high until just before transmission, the above
levels are output just before commencing transmission.

(2) Example of Connection of RS-485 

7-2-4. Terminal resistance

As SR73A and SR74A are not provided with terminal resistance,
connect a 510

resistance to only the last (the furthest from the

host) station. 

7-2-5. Control of 3-state output

(1) Since RS-422A and RS-485 employ the multi-drop system,

in order to prevent signals from colliding, transmission
output should be controlled to maintain high impedance
while communication is not being made or signals are being
received. 

(2) It should be controlled so that high impedance turns to the

normal state of output immediately before starting
transmission and high impedance is restored immediately
when transmission ends.  Because 3-state control is delayed
by about 3 msec. maximum from the transmission of the end
bit of the end character, a delay time of about 4 msec. should
be provided in case transmission is started immediately.

7-3. Setting of communication parameters

There are four communication-related parameters to be set as
shown below.  They are set by means of front keys except for
changing the communication mode from remote to local. 

[            ] Communication mode
[            ] Communication address
[            ] Communication data format
[            ] Communication rate
[            ] Delay

7-3-1. Communication mode selecting screen

(            )

(1) Local Mode (            )

The COM lamp on the front panel goes out to allow the
setting to be changed by the use of the front keys.  In
communication, only the change from local to remote and the
read commands are valid.

(2) Remote Mode (            )

The COM lamp on the front panel turns on and the
commands for read and write through communication
become valid.
Front key operation works only to change from remote to
local.

7-3-2. Communication address (

) setting screen

RS-422A and RS-485 allow connection of a plurality of
apparatuses but in fact, communication is carried out between two
apparatuses. Therefore, the address of each apparatus is
designated by a number between 00 and 99 so as to enable the
designated apparatus to respond.

7-3-3. Communication data format (

) selecting screen

Select data format of communication from 7b_E (data bit length

: 7 bits, parity : even, stop bit : 1) or 8b_n (data bit length : 8bits,
parity : none, stop bit : 1)

7-3-4. Communication rate (

) selecting screen

A rate of transmission from the controller to the host is selected
from among 1200, 2400, 4800 and 9600 bps. 

7-3-5. Delay (

) setting screen

In the case of RS-485, a minimum delay time for transmission
from receiving a communication command is set.  Delay time is a
set value (0~255) 

× 

0.1 msec.  Nevertheless, actual delay time

includes time for processing the command added to the above
delay time. 

7-4. Communication protocol 

7-4-1. Communication procedure

Communication is carried out for each block and the
communication right alternates between the controller and the
host from block to block.

7-4-2. Explanation of block 

(1) The data format in one block is shown below:

: Start character• • • • • @(40H)  Shows the start of a

block.

T x D+
T x D-
R x D+
R x D-
SG

SD+
SD-
RD+
RD-
SG

2
3
4
5
1

Shielding wire

terminal No.

SR73A and 74A Controllers

Line converter
FG (Earthing for protection) 

(+)

(-)

 SG

(+)

(-)

 SG

(+)

(-)

 SG

2
3
1

2
3
1

Shielding wire

Host computer 
FG (Earthing for protection)

terminal No.

SR73A and 74A Controllers 1

terminal No.

SR73A and 74A Controllers 2

Note:

If terminal resistance is connected to two or more,
correct action is not guaranteed.

Host computer

Transmitting command block

Returning response block

Transmitting command block

(Reading)

(Reading)

Returning response block

(Reading)

(Reading)

Controller (SR73A· 74A)

Transmission

Transmission

Response

Response

@

Higher
position

Lower
position 

Higher
position

Lower
position 

Text 

:

CR

1

2

3

4

5

6

Terminal resistance (510

)

Summary of Contents for SR73A Series

Page 1: ...o the instrument On the terminal nameplate affixed to the case of your instrument the mark is printed This is to warn you of the risk of electrical shock which may result if the charger is touched while it is energized A means to allow the power to be turned off such as a switch or a breaker should be installed in the external power circuit to be connected to the power terminal of the instrument F...

Page 2: ... 14 8 Specifications 15 4 1 Introduction 1 1 Check before use This product has been fully checked for quality assurance prior to shipment Nevertheless you are requested to make sure that there is no error damage or shortage of delivered items by confirming the model codes and checking the external view of the product and the number of accessories Confirmation of Model Codes Check the model codes s...

Page 3: ...th 48 height 91 6 width 44 6 Dimension of current transformer CT for heater break alarm For 0 30A CTL 6 S For 0 50A CTL 12 S36 8 unit mm 2 5 Wiring 1 Wiring operation should be done according to the instruction for the terminal arrangement in section 2 6 Exercise care that no wrong connection is made 2 Crimp terminal should accommodate the M3 5 screw and should have a width of less than 7mm 3 For ...

Page 4: ...nitor LED green On selection by ON turns on AT waiting key flashes on AT execution 3 AH alarm output monitor LED red Turns on for higher limit alarm output ON 4 AL HB alarm output monitor LED red Turns on for lower alarm output ON or heater break alarm ON 5 MAN manual control output monitor LED green Flashes when control output is in manual operation 6 STBY control output stop monitor LED green Tu...

Page 5: ... decimal point in the rightmost position on the top row flashes Press the or key to change the lower limit value and press the key to register the data Upon registering the lower limit value data the decimal point in the rightmost digit in the bottom row begins to flash Change the higher limit value by pressing the or key and register it by means of the key Upon registering the higher limit value ...

Page 6: ...ualoperation 0 100 Themeasuredvalue PV isdisplayedonthetopandthecontroloutput valueonthebottom PressingtheMANkeyonthisscreenswitches autotomanualandviceversa RefertoItem4 6 1 fordetail Control execution stop selecting screen Initialvalue EXEC Settingrange EXEC STBY Execution orstop ofcontrolisselected RefertoItem4 6 2 fordetail AT auto tuning action control screen Initialvalue OFF Settingrange OFF...

Page 7: ...ockissetonlockNo 1 2or3 noselectioncanbeperformedevenifthedigitpointis flashing Digits and arenotshownincaseofnooption Digitsof and arenotdisplayed Measuring range code select digit Initialvalue Multi05 Voltage V 81 Current95fixed Selectingtwodigitsfrom 4 5 Measuringrangecodetable Control output characteristic select digit Initialvalue RA heatingcharacteristics DA coolingcharacteristics RefertoIte...

Page 8: ...the higher limit value is forced to be the lower limit value 1 Therefore the higher limit value cannot be set to be less than the lower limit value 1 ENT Note Moving to another screen while maintaining the manual mode is possible In this case it should be noted that control output is made manually The apparatus is in the manual mode when the MAN monitor LED is flashing ENT 6 1 14 Soft Start Time S...

Page 9: ...m option is added and the lower limit alarm of the alarm type select digit on the function selecting screen of the mode 2 group screen group is selected Lower limit deviation value alarm is output for measured value to be less than set value alarm set value For lower limit deviation value alarm if set value alarm set value is less than the lower limit of the measuring range the action point is low...

Page 10: ...nd 74A series two types of communication interface RS 422A and RS 485 are available Each enables a personal computer or the like to set and read various data by the use of signals which conform with EIA standards RS 422A and RS 485 are communication standards established by the Electric Industries Association EIA which are meant for electrical or mechanical matters the so called hardware but not f...

Page 11: ...ront panel turns on and the commands for read and write through communication become valid Front key operation works only to change from remote to local 7 3 2 Communication address setting screen RS 422A and RS 485 allow connection of a plurality of apparatuses but in fact communication is carried out between two apparatuses Therefore the address of each apparatus is designated by a number between...

Page 12: ... value including a code is less than six characters 0 is inserted between the code and the figure or figures to make the value six characters When a code is excluded each of the 5 characters is a figure or a decimal point Examples of numerical data 1 Command The text format of read data contains only of a command of two characters Command Contents of Read Data PV value Execution SV value 1 Control...

Page 13: ...No did not match The end character was not CR 0DH A hardware error such as a framing error overrun or a parity error occurred 7 5 5 Restrictions by commands etc 1 Restrictions by Read Command Upon receiving the D1 read command the status of unequipped options AH AL HB SB become 0 30H 2 Restrictions by Write Command In the case of P OFF and Y and P output write data of E2 write command of manual ou...

Page 14: ...xt Data 3AH BCC CR 0DH Higher position Lower position Higher position Lower position Received data Transmitted data D1 D1 STBY MAN AH AL AT SB 0 30H or 1 31H PV value SV value Output value Received data Transmitted data D2 D2 Set value of AH Set value of AL Received data Transmitted data D3 D3 CT current value Set value of HB Received data Transmitted data D4 D4 Set value of SB Received data Trans...

Page 15: ... Sampling cycle 0 5 sec PV bias range 200 unit PV filter 0 100 sec 0 without filter Control Control mode Auto tuning PID ON OFF control Proportional band P Off 0 1 999 9 FS Off setting On Off action Integral time I Off 1 6000 sec Off setting P PD action Derivative time D Off 1 3600 sec Off setting P PI action Manual reset MR 50 0 50 0 Valid when P OFF and I OFF Output limiter Lower limit limiter 0...

Page 16: ...tact type or the SSR drive voltage type Alarm action Heater amperage detected by externally attached CT except 0 5V DC input Alarm output On upon detection of heater break while control output is On Current setting range Off 0 1 50 0A Alarm action stops when Off is set or Off 1 500A when 0 5 V DC for CT input is selected Setting resolution 0 1A or 1A Amperage display 0 0 55 0A or 0 550A Display ac...

Reviews: