(7) Setting of Position at the Time of Input Error
Screen for setting degree of opening
against input error
Initial value: 0%
Setting range: 0~100%
Set a value within the setting range.
Setting is possible only when a value of
position is selected as the setting for input
error.
The set value of position is limited by
higher/lower limit position limiters.
(8) Analog Output Setting
Analog output setting screen
Initial value:
Select from the following shown on the screen:
: Input is output.
: Position is output.
Note:
When analog output is changed on this
screen, higher and lower limit values of analog
output are initialized.
Lower limit side analog output setting
screen
Initial value: 0%
Setting range: 0~100%
Inversed scale is possible
(lower limit value
≠
higher limit value, though).
Higher limit side analog output setting
screen
Initial value: 100%
Setting range: 0~100%
Inversed scale is possible
(lower limit value
≠
higher limit value, though).
(9) Communication Setting
For the communication mode, please refer to the
communication instruction manual provided
separately.
Communication setting screen
Initial value:
Select from the following:
: Communication local mode (initial value)
: Communication mode
Key operation can make a change only from
the communication mode to the communica-
tion local mode.
In communication mode, keylock is effective
on all the setting screens except manual
operation.
Communication address setting screen
Initial value: 1
Setting range: 1~99
In case a plurality of controllers are linked for
communication, addresses need to be set
individually.
to the 1-19 screen
1-18
1-17
1-16
1-15
1-14
1-13
Communication rate setting screen
Initial value:
Set a value from the following shown on the
screen:
: 1200 bps (initial value)
: 2400 bps
: 4800 bps
: 9600 bps
: 19200 bps
The speed of communication should be set
correspondingly to that of the host computer.
Pressing the key for 3 seconds changes
the present speed of communication forcibly
to interrupt communication and to change to
the local mode. To restart communication, the
speed should be set correspondingly to that of
the host computer.
Communication data format setting screen
Initial value:
Select from the following:
: 7E1
: 7E2
: 7N1
: 7N2
: 8E1
: 8E2
: 8N1
: 8N2
The length of data bits, parity and the length
of stop bits are set.
Communication control code setting screen
Initial value: 1
Setting range: 1, 2 and 3
Select from the following shown on the screen:
: STX_ETX_CR
: STX_ETX_CRLF
: @_:_CR
A communication control code is set.
Communication BCC check setting screen
Initial value: 1
Setting range: 1, 2, 3 and 4
Select from the following shown on the screen:
: ADD
: ADD_two' s cmp
: XOR
: None
A BCC processing method to be used in
BCC checking is selected.
Communication memory mode setting
screen
Initial value:
Select from the following shown on the screen:
: EEPROM (initial value)
Data is written in memory.
: RAM
Data is written in RAM.
to the 1-24 screen
1-22
1-23
1-21
1-20
1-19
ENT