- 11 -
0-0 basic screen
0-1 Operation/Stand-by
screen
Operation/Stand-by
Operation
Select Stand-by
When suspension (standby) is registered
by means of the key, the STBY lamp
lights.
ENT
Stand-by
Switch from operation to stand-by:
Pressing
the key on the 0-1 operation/stand-by screen turns the display to
as shown above. When the
key is pressed,
the decimal point goes out and the STBY lamp lights. Then the operation is suspended.
Switch from stand-by to operation:
Pressing
the key on the 0-1 operation/stand-by screen turns the display to
. When the
key is pressed, the decimal
point as well as the STBY lamp goes out and operation is resumed.
Note on switching:
When Stop (
) is selected for external control input DI, switching by the use of front panel keys is not possible.
(4) Setting of Event Set Value
[0-2, 0-3, 0-4 screen, initial value:
setting range: 0 ~ 100%]
In case the optional event output (3 points) function is added, it is possible to select different events and contact outputs are produced
from the 3 points of EV1, EV2 and EV3.
Setting of Event Type
Before the setting, first set the event type.
Set the event type from "1-1 event 1 type setting screen", "1-4 Event 2 type setting screen" "1-7 event 3 type setting screen" in screen
group 1. (When an event type is changed the set value will be initialized, so reset becomes necessary.)
Setting is possible when 4 types of events allowing event set values to be set, i.e., higher and lower limits of position and higher and
lower limits of inputs as shown below:
4 types of alarms
: Lower limit of position,
: Higher limit of position,
: Lower limit of input,
: Higher limit of input can be set when the
setting is complete.
Display of screen only
: No setting
: Operation
: Manual
: Position error
: Input error
: Control Loop error
Event Set Value Setting (Use the table below for reference in setting.)
Code
Type
None
No event action
To be output during automatic operation.
To be output during manual operation.
To be output when position value lowers
below a set position.
To be output when position value exceeds
a set position.
To be output when control input value falls
below a set value.
To be output when control input value
exceeds a set value.
To be output when position value exceeds set
values for position error range.
To be output when control input value falls
below -10% or e110%.
To be output when feedback potentiometer
input signal does not correspond to control
output.
Position lower
limit value
Position higher
limit value
Control input
lower limit value
Control input
higher limit value
Automatic
operation
Manual
operation
Position error
Control input
error
Control loop
error
Description
Initial value
Automatic operation
Manual
Setting range
Code display
0%
0
~ 100%
100%
0
~ 100%
0%
0
~ 100%
100%
0
~ 100%
Code display
Code display
Code display
Code display
Code display
: Effective (Action, depending on condition)
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
Stand-by
Operation
DI