- 16 -
On each of the following screens, a value within
a setting range or an item from those displayed
is selected and set.
(3) Event Setting
Event 1 type setting screen
Initial value:
Select from the following types shown on the
screen.
: No setting (initial value)
: Lower limit side degree of opening
: Higher limit side degree of opening
: Lower limit side input
: Higher limit side input
: Automatic
: Manual
: degree of opening error
: Input error
: Control loop error
Note:
However, a set value is initialized
when the type of event is changed.
Event 1 hysteresis setting screen
Initial value: 0.1%
Setting range: 0.1~5.0%
Select a value within the setting range.
Setting is possible only when the event is
higher and lower limit alarm.
( , , , )
Event 1 stand-by action setting screen
Initial value:
Select either of the following:
: With stand-by action
: Without stand-by action
Setting is possible only when the event is
higher and lower than the limit alarm.
( , , , )
Event 2 type setting screen
Initial value:
The same as event 1.
Event 2 hysteresis setting screen
Initial value: 0.1%
Setting range: 0.1~5.0%
The same as event 1.
Event 2 stand-by action setting screen
Initial value:
Select either of the following:
: With stand-by action
: Without stand-by action
The same as event 1
Key Operation
Screen Group 1
1-0 automatic adjustment screen or 1-00 manual adjustment
screen is the starting screen.
The and keys are used for selection on a screen and
an item or a numerical value is registered by means of the
key. To return to the preceding setting screen, press the
key. When the key is pressed, the 1-0 or 1-00 basic
screen is returned.
1-1
ENT
DISP
AUTO
MAN
1-2
1-3
1-4
1-6
1-5
to the 1-7 screen
Event 3 type setting screen
Initial value:
The same as event 1.
Event 3 hysteresis setting screen
Initial value: 0.1%
Setting range: 0.1~5.0%
The same as event 1.
Event 3 stand-by action setting screen
Initial value:
Select either of the following shown on the
screen:
: With stand-by action
: Without stand-by action
The same as event 1
(4)
Setting of Motor Action at the Time of
Position
Error
Screen for setting motor action at the Time
of position error
Initial value:
Select from the following shown on the screen:
: Motor stop
: Motor close
: Motor open
Position error: When the value of position is
less than the set range of position errors
(Po_LL) and when the value of position is
more than the set range of position errors
(Po_HH).
During manual operation, action setting upon
occurrence of a position error is not valid
since manual operation is given the first
priority.
In case of SSR position error output, the
motor speed is put in action.
(5)
Screen for Setting Motor Action Time at the
time of Position Error
Screen for setting motor action time at the
time of position error
Initial value: 300 seconds
Setting range: 1~300 seconds
Set a time within the setting range.
Setting is possible only when "open" or
"close" has been set against position degree.
Control output will output for each setting time.
(6)
Setting of Motor Action at the Time of Input
Error
Screen for setting motor action at the time
off input error
Initial value:
Select from the following shown on the screen:
: Action in response to abnormal input
signal
: Motor stop
: Motor to be adjusted to set degree of
opening
Input error: An input error means that input
data is below
-
10% (In-LL displayed) or
above 110% (In-HH).
During manual operation, suspension of
operation and control with present value of
position, input error is not dealt with.
1-8
1-7
to the 1-13 screen
1-9
1-10
1-11
1-12