7: Using the Shark® 100B Meter
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
You can also change the following fields:
• Network Mask - the subnet mask. The default is 255.255.255.0.
• Default Gateway - the IP address of the gateway. The default is 10.0.0.224.
• BACnet UDP Port - the BACnet/IP UDP port number. The default is 47808. In
some cases, e.g., if it is necessary for two groups of BACnet devices to be set up
independently on the same IP subnet, the UDP port can be configured locally to
a different value.
• BACnet Device Number - a numeric code used to identify the meter. This number
is auto-generated from the MAC address.
• BBMD IP Address - when a BBMD IP address is entered here it enables Foreign
Device mode.
• BACnet Device Location/Application - a readable string of up to 63 characters
that you can use to find the Device Object Name.