Revision – MOVIGEAR
®
performance
33
"DRIVE" status LED
LED
Operating status/
Meaning
Measure
Fault
code
Subfault code
–
Off
Not ready for operation
Line voltage absent.
Switch on the line
voltage.
Yellow
Flashes very rap-
idly, 4 Hz
Not ready for operation
Initialization phase
Wait for the initializa-
tion to be completed.
Yellow
Flashes 1 Hz
Ready but unit inhibited
The "STO" signal is active.
Deactivate the
"STO” signal.
Yellow
Flashes slowly,
0.5 Hz
Ready for operation, but
manual mode/local mode,
device inhibited
Line voltage is OK.
–
Yellow
Flashes rapidly,
2 Hz
Ready
Deactivation of DynaStop
®
without drive enable is active.
–
Yellow
Steady light
Ready but unit inhibited
Line voltage is OK.
The output stage is locked.
–
Green
Flashes slowly,
0.5 Hz
Unit enabled, but condition
manual mode/local mode
The output stage is enabled.
The motor is in operation.
–
Green
Flashes very rap-
idly, 4 Hz
Unit enabled, but current limit
active.
The drive is at the current
limit.
Reduce the load.
Green
Steady light
Unit enabled.
The output stage is enabled.
The motor is in operation.
–
Yellow/red
Flashes with chan-
ging colors, 1 Hz
(2 × yellow, 2 × red)
Ready
A displaying fault is present.
The output stage is locked.
Consult the “Fault
table” chapter for
possible measures
to be taken.
Green/red
Flashes with chan-
ging colors, 1 Hz
(2 × green, 2 × red)
Ready
A displaying fault is present.
The output stage is enabled.
The motor is in operation.
Consult the “Fault
table” chapter for
possible measures
to be taken.