4
Project Planning and Startup
Configuring a PROFIBUS-DP master
Manual – MOVI-PLC
®
basic DHP11B.. controller
39
The SEW drive is available under the following path in the hardware catalog:
PROFIBUS-DP
+--Additional PERIPHERAL UNITS
+--Drives
+---SEW
+--DPV1
+---MOVI-PLC
The installation of the new GSD file is now complete.
Project planning
with STEP7
Proceed as follows to configure the MOVI-PLC
®
basic
DHP11B.. controller with the
PROFIBUS-DP interface:
1. Add the interface module with the name "MOVI-PLC" to the PROFIBUS structure
and assign the PROFIBUS station address (
Æ
following figure).
58365AXX
0
0
I